• SPD for general structured cabling networks,60 V, LPZ 0-1 and higher.

For general structured cabling networks.

  • Combined (2-stage) SPD for general structured cabling networks.
  • LPZ 0 to LPZ 1 boundary installation.
  • To protect devices working with signals over twisted pairs up to 60 V.


Specifications:


Parameter name

Parametervalue

Type of SPD

D1,C2,C3

Location of SPD

ST 1+2+3

Mounting

DIN rail 35 mm

Maximum operating voltage core-core

Uc

60,00 V DC

Maximum operating voltage pair-pair (POE)

Uc

60,00 V DC

Nominal load current per core at 25 °C

IL

0.5 A

Treshold frequency core-core

f

250.00 MHz

Insertion attenuation at treshhold frequency

1.50 dB

C2 nominal discharge current (8/20 µs) core-core

In

0.15 kA

D1 total discharge current (10/350 µs) cores-PE

ITotal

2.00 kA

 

C2 total discharge current (8/20 µs) cores-PE

ITotal

10.00 kA

C2 voltage protection level mode core-core (@Uoc/In)

Up

120,00 V (0,3 kV / 0,15 kA)

C2 voltage protection level mode core-PE (@Uoc/In)

Up

700,00 V (2,5 kV / 1,25 kA)

C2 voltage protection level mode pair-pair (POE) (@Uoc/In)

Up

90,00 V (0,3 kV / 0,15 kA)

C3 voltage protection level mode core-core (@In - 1 kV/µs)

Up

110,00 V (10 A)

C3 voltage protection level mode core-PE (@In - 1 kV/µs)

Up

500,00 V (10 A)

C3 voltage protection level mode pair-pair (POE) (@In - 1 kV/µs)

Up

85,00 V (10 A)

Response time core-core

ta

1 ns

Response time core-PE

ta

100 ns

Connection (input - output)

RJ 45/RJ 45

Degree of protection

IP 30 (without connectors IP 10)

Range of ambient temperatures (min/max)

-10 / 50 °C

Humidity

15 - 85 %

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC000943

Customs tariff number

85363010

EAN

8595090570691




























Dimensions:




Write a review

Note: HTML is not translated!
Captcha

SPD for general structured cabling networks,60 V, LPZ 0-1 and higher.

0 reviews / Write a review

* Required fields



Related Product

Lightning current arrester for 3-phase TN-S system, 100 kA (10/350 µs)

Lightning current arrester for 3-phase TN-S system, 100 kA (10/350 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.Four-pole high ..

Lightning current arrester for 3-phase TN-S system, 100 kA (10/350 µs)

Lightning current arrester for 3-phase TN-S system, 100 kA (10/350 µs)

Pluggable module, visual fault signalling, module locking.Four-pole high performance lightning cur..

Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)

Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.Three-pole high..

Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)

Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)

Pluggable module, visual fault signalling, module locking.Three-pole high performance lightning cu..