For general
structured cabling networks.
- Combined
(2-stage) SPD for general structured cabling networks.
- LPZ
0 to LPZ 1 boundary installation.
- To protect devices working with signals over twisted pairs up to 60 V.
Specifications:
Parameter name |
Parametervalue |
|||
Type
of SPD |
D1,C2,C3 |
|||
Location
of SPD |
ST 1+2+3 |
|||
Mounting |
DIN rail 35 mm |
|||
Maximum
operating voltage core-core |
Uc |
60,00 V DC |
||
Maximum
operating voltage pair-pair (POE) |
Uc |
60,00 V DC |
||
Nominal
load current per core at 25 °C |
IL |
0.5 A |
||
Treshold
frequency core-core |
f |
250.00 MHz |
||
Insertion
attenuation at treshhold frequency |
1.50 dB |
|||
C2
nominal discharge current (8/20 µs) core-core |
In |
0.15 kA |
||
D1
total discharge current (10/350 µs) cores-PE |
ITotal |
2.00 kA |
|
|
C2
total discharge current (8/20 µs) cores-PE |
ITotal |
10.00 kA |
||
C2
voltage protection level mode core-core (@Uoc/In) |
Up |
120,00 V (0,3 kV / 0,15 kA) |
||
C2
voltage protection level mode core-PE (@Uoc/In) |
Up |
700,00 V (2,5 kV / 1,25 kA) |
||
C2
voltage protection level mode pair-pair (POE) (@Uoc/In) |
Up |
90,00 V (0,3 kV / 0,15 kA) |
||
C3
voltage protection level mode core-core (@In - 1 kV/µs) |
Up |
110,00 V (10 A) |
||
C3
voltage protection level mode core-PE (@In - 1 kV/µs) |
Up |
500,00 V (10 A) |
||
C3
voltage protection level mode pair-pair (POE) (@In - 1 kV/µs) |
Up |
85,00 V (10 A) |
||
Response
time core-core |
ta |
1 ns |
||
Response
time core-PE |
ta |
100 ns |
||
Connection
(input - output) |
RJ 45/RJ 45 |
|||
Degree
of protection |
IP 30 (without connectors IP 10) |
|||
Range
of ambient temperatures (min/max) |
-10 / 50 °C |
|||
Humidity |
15 - 85 % |
|||
According
to standard |
EN 61643-21+A1,A2:2013, IEC
61643-21+A1,A2:2012 |
|||
ETIM
Class |
EC000943 |
|||
Customs
tariff number |
85363010 |
|||
EAN |
8595090570691 |
Dimensions:
SPD for general structured cabling networks,60 V, LPZ 0-1 and higher.
Related Product
Lightning current arrester for 3-phase TN-S system, 100 kA (10/350 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Four-pole high ..
Lightning current arrester for 3-phase TN-S system, 100 kA (10/350 µs)
Pluggable module, visual fault signalling, module locking.Four-pole high performance lightning cur..
Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Three-pole high..
Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)
Pluggable module, visual fault signalling, module locking.Three-pole high performance lightning cu..