• SPD for general structured cabling networks ,60V, LPZ 0-1 and higher

For high-speed general structured cabling networks.

  • Combined (2-stage) SPD for high-speed general structured cabling networks.
  • LPZ 0 to LPZ 1 boundary installation.
  • To protect devices working with signals over twisted pairs up to 60V.


Specifications:


Parameter name

Parameter value

Type of SPD

D1,C2,C3

Location of SPD

ST 1+2+3

Mounting

DIN rail 35 mm

Maximum operating voltage core-core

Uc

60,00 V DC

Maximum operating voltage pair-pair (POE)

Uc

60,00 V DC

Nominal load current per core at 25 °C

IL

0.5 A

Treshold frequency core-core

f

500.00 MHz

Insertion attenuation at treshhold frequency

2.50 dB

C2 nominal discharge current (8/20 µs) core-core

In

0.15 kA

D1 total discharge current (10/350 µs) cores-PE

ITotal

2.00 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

10.00 kA

C2 voltage protection level mode core-core (@Uoc/In)

Up

120,00 V (0,3 kV / 0,15 kA)

C2 voltage protection level mode core-PE (@Uoc/In)

Up

700,00 V (2,5 kV / 1,25 kA)

C2 voltage protection level mode pair-pair (POE) (@Uoc/In)

Up

90,00 V (0,3 kV / 0,15 kA)

C3 voltage protection level mode core-core (@In - 1 kV/µs)

Up

110,00 V (10 A)

C3 voltage protection level mode core-PE (@In - 1 kV/µs)

Up

500,00 V (10 A)

C3 voltage protection level mode pair-pair (POE) (@In - 1 kV/µs)

Up

85,00 V (10 A)

Response time core-core

ta

1 ns

Response time core-PE

ta

100 ns

Connection (input - output)

RJ 45/RJ 45

Degree of protection

IP 30 (without connectors IP 10)

Range of ambient temperatures (min/max)

-10 / 50 °C

Humidity

15 - 85 %

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC000943

Customs tariff number

85363010

EAN

8595090570707



Dimensions:



Write a review

Note: HTML is not translated!
Captcha

SPD for general structured cabling networks ,60V, LPZ 0-1 and higher

0 reviews / Write a review

* Required fields



Related Product

Lightning current arrester for coaxial lines (antennas), 360 V DC

Lightning current arrester for coaxial lines (antennas), 360 V DC

Connectors N 50 Ohm.Lightning current arrester for coaxial line.Iinstallation at the boundary of LPZ..

Lightning current arrester for coaxial line, 360 V DC

Lightning current arrester for coaxial line, 360 V DC

Connectors N 50 Ohm.Lightning current arrester for coaxial line.Installation at the boundary of LPZ ..

Lightning current arrester for coaxial lines (antennas), up to 250V DC

Lightning current arrester for coaxial lines (antennas), up to 250V DC

N connectors, 50 Ohm.Lightning current arrester for coaxial line.Installation at the boundary of LPZ..

Lightning current arrester for coaxial lines (antennas), 250V DC

Lightning current arrester for coaxial lines (antennas), 250V DC

N connectors, 50 Ohm.Lightning current arrester for coaxial line.Installation at the boundary of LP..