RJ45 + SV
connectors.
- Two-stage
surge protection device for Ethernet protection, combined with PoE protection
including the injector.
- Installed
at the entry point into the building object, near the equipment to be
protected, at the interface of the LPZ 0 and LPZ 1 and higher zones.
- For use in Ethernet Cat. 6 lines with PoE (Power over Ethernet), operating in A and B modes, to protect them from peak overvoltages.
Specifications:
Parameter name |
Parameter
value |
|
Type of SPD |
D1,C2,C3 |
|
Location of SPD |
ST
1+2+3 |
|
Mounting |
DIN
rail 35 mm |
|
Maximum operating voltage |
Uc |
8.50
V DC |
Maximum operating voltage POE |
Uc |
58.00
V DC |
Nominal load current per core at 25
°C |
IL |
0.5
A |
Treshold frequency core-core |
f |
250.00
MHz |
Insertion attenuation at treshhold
frequency |
1.20
dB |
|
D1 total discharge current (10/350
µs) cores-PE |
ITotal |
2.00
kA |
C2 nominal discharge current (8/20
µs) per core |
In |
0.15
kA |
C2 total discharge current (8/20 µs)
cores-PE |
ITotal |
10.00
kA |
C2 voltage protection level mode
(POE) at In = 1,25 kA |
Uc |
90.00
V |
C2 voltage protection level mode
core-PE at In = 1,25 kA |
Up |
700.00
V |
C2 voltage protection level mode
core-core at In |
Up |
70
V |
C3 voltage protection level mode
(POE) at 1 kV/µs |
80.00
V |
|
C3 voltage protection level mode
core-PE at 1 kV/µs |
Up |
500
V |
C3 voltage protection level mode
core-core at 1 kV/µs |
Up |
80
V |
Response time core-core |
ta |
1
ns |
Response time core-PE |
ta |
100
ns |
Connection (input - output) |
RJ
45/RJ 45 |
|
Degree of protection |
IP
20 |
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
Humidity |
5
- 95 % |
|
According to standard |
EN
61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 |
|
Customs tariff number |
85363030 |
|
EAN |
8595090566205 |
Dimensions:
SPD for Ethernet 1 Gbite/s (Cat.6) with PoE, 2 kA (10/350 µs)
Related Product
Lightning current arrester for 3-phase TN-S system, 100 kA (10/350 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Four-pole high ..
Lightning current arrester for 3-phase TN-S system, 100 kA (10/350 µs)
Pluggable module, visual fault signalling, module locking.Four-pole high performance lightning cur..
Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Three-pole high..
Lightning current arrester for 3-phase TN-C system, 75 kA (10/350 µs)
Pluggable module, visual fault signalling, module locking.Three-pole high performance lightning cu..