• Surge protection for Ethernet 1 Gbit/s (Cat. 6) or 10 Gbit/s (Cat. 6A), 2 kA (10/350 µs).

RJ45 sockets, PCB, with injector.

  • Combination of coarse and fine protection of Ethernet line with PoE.
  • Instalation at the entry of the line into building and close to protected equipment, at the boundary of LPZ 0 and LPZ 1 or higher.
  • For protection of Ethernet line Cat. 6 or Cat. 6A with PoE (Power over Ethernet) in mode A or B against surge voltage.
  • For assembly to DL-CS-RACK-1U-INJECTOR.


Specifications:


Parameter name

Parameter value

Type of SPD

D1,C2,C3

Location of SPD

ST 1+2+3

Mounting

DL-CS-RACK-1U-INJECTOR

Maximum operating voltage

Uc

8.50 V DC

Maximum operating voltage POE

Uc

58.00 V DC

Nominal load current per core at 25 °C

IL

0.5 A

Treshold frequency core-core

f

250.00 MHz

Insertion attenuation at treshhold frequency

1.20 dB

D1 total discharge current (10/350 µs) cores-PE

ITotal

2.00 kA

C2 nominal discharge current (8/20 µs) per core

In

0.15 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

10.00 kA

C2 voltage protection level mode core-PE at In = 1,25 kA

Up

700.00 V

C2 voltage protection level mode core-core at In

Up

70 V

C3 voltage protection level mode (POE) at 1 kV/µs

80.00 V

C2 voltage protection level mode (POE) at In = 1,25 kA

Uc

90.00 V

C3 voltage protection level mode core-PE at 1 kV/µs

Up

500 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

80 V

Response time core-core

ta

1 ns

Response time core-PE

ta

100 ns

Connection (input - output)

RJ 45/RJ 45

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

Customs tariff number

85363030

EAN

8595090565703


Dimensions:



Write a review

Note: HTML is not translated!
Captcha

Surge protection for Ethernet 1 Gbit/s (Cat. 6) or 10 Gbit/s (Cat. 6A), 2 kA (10/350 µs).

0 reviews / Write a review

* Required fields



Related Product

Replacement module for BDG-024-V/1-xRx

Replacement module for BDG-024-V/1-xRx

SPD - for data, signalling and telecommunications lines / I&C / Spare modules.Replacement module..

AC diverter ,for suppression of AC voltage

AC diverter ,for suppression of AC voltage

SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..

Digital tester for status monitor of SPDs

Digital tester for status monitor of SPDs

Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..

Automatic VLD class 2 tester

Automatic VLD class 2 tester

Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..