• Surge protection for telecommunication line, 170 V

For LSA-PLUS separating strips.

  • Combination of coarse and fine protection of 2-core telecommunication lines.
  • Installation close to protected equipment.
  • For protection of telecommunication lines against impact of surge voltage.
  • Coarse and fine surge protection in differential mode (core – core) and coarse protection in common mode (core – PE).


Specifications:


Parameter name

Parameter value

Type of SPD

C2,C3

Location of SPD

ST 2+3

Mounting

LSA disconnection rail

Maximum operating voltage

Uc

120.00 V AC

Maximum operating voltage

Uc

170.00 V DC

Nominal load current

IL

0.500 A

Serial resistance per core

R

1.60 Ω

C2 nominal discharge current (8/20 µs) per core

In

5.00 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

10.00 kA

C2 voltage protection level mode core-PE at In

Up

400 V

C2 voltage protection level mode core-core at In

Up

310 V

C3 voltage protection level mode core-PE at 1 kV/µs

Up

350 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

230 V

Response time core-core

ta

1 ns

Response time core-PE

ta

100 ns

Connection (input - output)

LSA disconnection rail

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 70 °C

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001625

Accessories

grounding rail

Customs tariff number

85363010

EAN

8595090551737



Dimensions:






Write a review

Note: HTML is not translated!
Captcha

Surge protection for telecommunication line, 170 V

0 reviews / Write a review

* Required fields



Related Product

Replacement module for BDG-024-V/1-xRx

Replacement module for BDG-024-V/1-xRx

SPD - for data, signalling and telecommunications lines / I&C / Spare modules.Replacement module..

AC diverter ,for suppression of AC voltage

AC diverter ,for suppression of AC voltage

SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..

Digital tester for status monitor of SPDs

Digital tester for status monitor of SPDs

Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..

Automatic VLD class 2 tester

Automatic VLD class 2 tester

Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..