• Combination of lightning current and surge arrester ,100 kA

Pluggable module, visual fault signalling, module locking, remote fault signalling.

  • Combination of three-pole high performance lightning current arrester and encapsulated efficiency spark gap, connected in the 3+1 mode.
  • Installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards.
  • For protection against impact of direct or indirect lightning strikes in wide range of applications – office or industrial buildings.
  • No follow current, zero leakage current.
  • With integrated backup fuse.


Specifications:

Parameter name

Parameter value

Type of SPD

T1,T2

Mounting

DIN rail 35 mm

Nominal voltage

Un

230 V AC

Maximum operating voltage L-N

Uc

260.00 V AC

Maximum operating voltage N-PE

Uc

255.00 V AC

Type of network

TT|TN-S

Maximum overcurrent protection

-

Short-circuit current rating

ISCCR

50.0 kA

Lightning impulse current (10/350 µs) L-N

Iimp

25.00 kA

Lightning impulse current (10/350 µs) N-PE

Iimp

100.00 kA

Nominal discharge current (8/20 µs) L-N

In

30.00 kA

Nominal discharge current (8/20 µs) N-PE

In

100.00 kA

Maximum discharge current (8/20 µs) L-N

Imax

60.00 kA

Maximum discharge current (8/20 µs) N-PE

Imax

100.00 kA

Voltage protection level mode L-N

Up

1.50 kV

Voltage protection level mode L-PE

Up

2.20 kV

Voltage protection level mode N-PE

Up

1.50 kV

Ability to independently switch off the following current N-PE

Ifi

0.1 kA

Response time L-N

ta

100 ns

Response time N-PE

ta

100 ns

TOV 5 s L-N

335 V

TOV characteristic (TOV 5 s)

withstand

TOV 120 min L-N

440 V

TOV characteristic (120 min)

withstand

TOV 200 ms N-PE

1 200 V

TOV characteristic (TOV 200 ms)

withstand

Cross-section of connected conductors solid (min)

2.50 mm2

Cross-section of connected conductors solid (max)

50.00 mm2

Cross-section of connected conductors stranded (min)

2.50 mm2

Cross-section of connected conductors stranded (max)

35.00 mm2

Cross-section of remote indication conductors solid (max)

1.5 mm2

Cross-section of remote indication conductors stranded (max)

1.5 mm2

Fault indication L-N

red indication field

Fault indication N-PE

no

Remote indication

potential-free change-over contact

Remote indication contacts

250V/0,5A AC,250V/0,1A DC

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC001457

Plug module

FLP-B+C MAXI V/0|FLP-A100N V/0

Customs tariff number

85363090

EAN

8595090571186


Dimensions:






Write a review

Note: HTML is not translated!
Captcha

Combination of lightning current and surge arrester ,100 kA

0 reviews / Write a review

* Required fields



Related Product

Round Cable Entry 4"

Round Cable Entry 4"

19" divided vented panel with double layer brush, color black...

USB To RS-232 Adapter

USB To RS-232 Adapter

-Supports RS-232 serial interface-Proven performance in anti-electromagnetic interference (anti-EMI)..

KVMP 2-Port USB2.0 Mini Display Port Dual View Mini-TOSLINK

KVMP 2-Port USB2.0 Mini Display Port Dual View Mini-TOSLINK

-Mini DisplayPort 1.1a & HDCP compatible.-Superior video quality – enables up to 2560 x 1600 res..

Combination of lightning ,TN and TT, 25 kA (10/350 µs), 60 kA (8/20 µs)

Combination of lightning ,TN and TT, 25 kA (10/350 µs), 60 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking.High performance lightning current arres..