• Surge arrester , TN-S (120/240 V AC) , TN-C (120/208 V AC), 120 kA (8/20 µs)

Pluggable module, visual fault signalling, remote fault signalling.

  • Three-pole varistor surge arrester.
  • Installation to LV installations, especially to sub-distribution boards in TN-C systems.
  • For protection of the installations and equipments against impact of induced overvoltages during a lightning strike or switching overvoltages.


Specifications:


Parameter name

Parameter value

Type of SPD

T2

Mounting

DIN rail 35 mm

Nominal voltage

Un

120 V AC

Maximum operating voltage

Uc

150.00 V AC

Maximum operating voltage

Uc

200.00 V DC

Type of network

TN

Maximum overcurrent protection

160 A gL/gG

Short-circuit current rating

ISCCR

50.0 kA

Residual current

IPE

0.350 mA

Nominal discharge current (8/20 µs)

In

15.00 kA

Maximum discharge current (8/20 µs)

Imax

40.00 kA

Voltage protection level

Up

0.74 kV

Voltage protection level at 5 kA

Up

0.60 kV

Response time

ta

25 ns

TOV 5 s L-N

175 V

TOV characteristic (TOV 5 s)

withstand

Cross-section of connected conductors solid (min)

4.00 mm2

Cross-section of connected conductors solid (max)

35.00 mm2

Cross-section of connected conductors stranded (min)

4.00 mm2

Cross-section of connected conductors stranded (max)

25.00 mm2

Cross-section of remote indication conductors solid (max)

1.5 mm2

Cross-section of remote indication conductors stranded (max)

1.5 mm2

Fault indication

red indication field

Remote indication

potential-free change-over contact

Remote indication contacts

250V/0,5A AC,250V/0,1A DC

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC000941

Plug module

SLP-150 V/0

Customs tariff number

85363030

EAN

8595090574484


Dimensions:




Replacement module: SLP-150 V/0



Write a review

Note: HTML is not translated!
Captcha

Surge arrester , TN-S (120/240 V AC) , TN-C (120/208 V AC), 120 kA (8/20 µs)

0 reviews / Write a review

* Required fields



Related Product

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Spark gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 3+1 mode.Installa..

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

park gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 1+1 mode.Installat..

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of v..

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking.Combination of varistor lightning current ..