Replacement module for FLP-B+C MAXI V/x.
Specifications:
Parameter name |
Parameter value |
|
|
Type of SPD |
T1 |
|
|
Maximum operating voltage |
Uc |
260.00 V AC |
|
Short-circuit current rating |
ISCCR |
50.0 kA |
|
Lightning impulse current (10/350 µs) |
Iimp |
25.00 kA |
|
Nominal discharge current (8/20 µs) |
In |
30.00 kA |
|
Maximum discharge current (8/20 µs) |
Imax |
60.00 kA |
|
Voltage protection level |
Up |
1.50 kV |
|
Response time |
ta |
100 ns |
|
Fault indication |
red indication field |
|
|
ETIM Class |
EC000941 |
|
|
Customs tariff number |
85363090 |
|
|
EAN |
8595090535355 |