Pluggable module,
visual fault signalling.
- Varistor
surge arrester.
- Installation
to LV installations, especially to sub-distribution boards.
- For protection of the installations and equipments against impact of induced overvoltages during a lightning strike or switching overvoltages.
Specifications:
Parameter name |
Parameter
value |
|
Type of SPD |
T2 |
|
Mounting |
DIN
rail 35 mm |
|
Nominal voltage |
Un |
400
V AC |
Maximum operating voltage |
Uc |
440.00
V AC |
Maximum operating voltage |
Uc |
585.00
V DC |
Type of network |
TN |
|
Maximum overcurrent protection |
125
A gL/gG |
|
Short-circuit current rating |
ISCCR |
25.0
kA |
Nominal discharge current (8/20 µs) |
In |
20.00
kA |
Maximum discharge current (8/20 µs) |
Imax |
40.00
kA |
Voltage protection level |
Up |
1.90
kV |
Voltage protection level at 5 kA |
Up |
1.50
kV |
Response time |
ta |
25
ns |
TOV 5 s L-N |
580
V |
|
TOV characteristic (TOV 5 s) |
withstand |
|
Cross-section of connected
conductors solid (min) |
1.00
mm2 |
|
Cross-section of connected
conductors solid (max) |
35.00
mm2 |
|
Cross-section of connected
conductors stranded (min) |
1.00
mm2 |
|
Cross-section of connected
conductors stranded (max) |
25.00
mm2 |
|
Fault indication |
red
indication field |
|
Degree of protection |
IP
20 |
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
Humidity |
5
- 95 % |
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
ETIM Class |
EC000941 |
|
Plug module |
SLP-440
V/0 |
|
Customs tariff number |
85363030 |
|
EAN |
8595090518174 |
Dimensions:
Replacement module: SLP-440 V/0
Surge arrester ,TN and TT systems, 440 V AC, 40 kA (8/20 µs)
Related Product
Surge arrester , TN with fluctuating voltage , 120 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking.Three-pole varistor surge arrester.Insta..
Surge arrester for three-phase system TN-C, 120 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Three-pole vari..
Surge arrester for three-phase system TN-C, 120 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking.Three-pole varistor surge arrester.Insta..
Separating inductor (bridge) for coordination of SPDs, up to 32 A.
Coupling impedance.For coordination of SPDs type 1 and 2 or type 2 and 4.Specifications: ..