Visual fault signalling, 3 m power supply cord, CEE 7/7 plug type, on/off switch, RFI filter.
- Multiple socket outlet with integrated surge protection SPD Type 3 and RFi filter.
- For 19" RACK.
- For protection of information technology equipments against surge voltage and RF disturbance.
- Mounting height 1U.
- 5x socket outlet - French type.
Specifications:
Parameter name |
Parameter
value |
|
Type of SPD |
T3 |
|
Mounting |
19"
rack |
|
VF filter |
yes |
|
Nominal voltage |
Un |
230
V AC |
Maximum operating voltage |
Uc |
275.00
V AC |
Nominal load current |
IL |
16.000
A |
Type of network |
TN |
|
Maximum overcurrent protection |
16
A gL/gG or C 16 A |
|
Short-circuit current rating |
ISCCR |
6.0
kA |
Residual current |
IPE |
0.700
mA |
Filter attenuation at 1MHz (50 Ω//50
Ω/) unsymmetrical |
30
dB |
|
Nominal discharge current (8/20 µs)
L-N |
In |
3.00
kA |
Nominal discharge current (8/20 µs)
L+N-PE |
In |
5.00
kA |
Nominal discharge current (8/20 µs)
N-PE |
In |
3.00
kA |
Test voltage L-N |
Uoc |
6.0
kV |
Test voltage N-PE |
Uoc |
6.0
kV |
Test voltage L+N-PE |
Uoc |
10.0
kV |
Voltage protection level mode L-N |
Up |
1.20
kV |
Voltage protection level mode L-PE |
Up |
1.50
kV |
Voltage protection level mode N-PE |
Up |
1.50
kV |
Response time L-N |
ta |
25
ns |
Response time N-PE |
ta |
100
ns |
Fault indication |
red
indicator |
|
Degree of protection |
IP
40 |
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
ETIM Class |
EC000942 |
|
Customs tariff number |
85363010 |
|
EAN |
8595090558750 |
Dimensions:
Multi socket outlet RFi filter ,SPD Type 3 for 19" RACK
Related Product
Surge arrester , TN with fluctuating voltage , 120 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking.Three-pole varistor surge arrester.Insta..
Surge arrester for three-phase system TN-C, 120 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Three-pole vari..
Surge arrester for three-phase system TN-C, 120 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking.Three-pole varistor surge arrester.Insta..
Separating inductor (bridge) for coordination of SPDs, up to 32 A.
Coupling impedance.For coordination of SPDs type 1 and 2 or type 2 and 4.Specifications: ..