Pluggable module,
visual fault signalling, module locking.
- Three-pole
varistor surge arrester..
- Installation
to LV installations, especially to sub-distribution boards in TN, IT systems
- For
protection of the installations and equipments against impact of induced
overvoltages during a lightning strike or switching overvoltages.
- Suitable for the protection of wind farms and inverters.
Specifications:
Parameter name |
Parameter value |
|
Type of SPD |
T2 |
|
Mounting |
DIN rail
35 mm |
|
Nominal voltage |
Un |
230,00–690,00
V AC |
Maximum operating voltage |
Uc |
760.00 V
AC |
Maximum operating voltage of varistor |
880 V AC |
|
Type of network |
TN |
|
Maximum overcurrent protection |
100 A
gL/gG |
|
Short-circuit current rating |
ISCCR |
25.0 kA |
Nominal discharge current (8/20 µs) |
In |
20.00 kA |
Maximum discharge current (8/20 µs) |
Imax |
40.00 kA |
Voltage protection level |
Up |
3.20 kV |
Voltage protection level at 5 kA |
Up |
2.70 kV |
Response time |
ta |
25 ns |
Cross-section of connected conductors solid (min) |
1.00 mm2 |
|
Cross-section of connected conductors solid (max) |
35.00 mm2 |
|
Cross-section of connected conductors stranded (min) |
1.00 mm2 |
|
Cross-section of connected conductors stranded (max) |
25.00 mm2 |
|
Fault indication |
red
indication field |
|
Degree of protection |
IP 20 |
|
Range of ambient temperatures (min/max) |
-40 / 80
°C |
|
Humidity |
5 - 95 % |
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
ETIM Class |
EC000941 |
|
Plug module |
SLP-600
V/0 |
|
Customs tariff number |
85363030 |
|
EAN |
8595090560760 |
Dimensions:
Replacement module: SLP-600 V/0
Varistor surge arrester, TN and IT systems ,690 V AC, 120 kA (8/20
Related Product
Three-phase surge protection, TN and TT, 63 A
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of va..
Surge arrester for three-phase system TN-S, 160 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Four-pole varis..
Surge arrester for three-phase system TN-S, 160 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking.Fur-pole varistor surge arrester.Install..
Varistor surge arrester, TN and IT systems, 690 V AC, 120 kA (8/20)
Pluggable module, visual fault signalling, module locking.Three-pole varistor surge arrester.Insta..