Fault signalling
by supply interruption.
- Surge
arrester especially for LED lights.
- Installation
close to protected equipme in LV power circuits.
- Also for equipment in external part of building with high exposure level (according to IEEE C62.41.2).
Specifications:
ameter name |
Parameter
value |
|
Type of SPD |
T2,T3 |
|
Nominal voltage |
Un |
230
V AC |
Maximum operating voltage |
Uc |
320.00
V AC |
Nominal load current |
IL |
10.000
A |
Type of network |
TN|TT |
|
Maximum overcurrent protection |
32
A gL/gG or C 32 A |
|
Short-circuit current rating |
ISCCR |
3.0
kA |
Residual current |
IPE |
0.004
mA |
Nominal discharge current (8/20 µs)
L-N |
In |
5.00
kA |
Nominal discharge current (8/20 µs)
N-PE |
In |
5.00
kA |
Maximum discharge current (8/20 µs)
L-N |
Imax |
10.00
kA |
Maximum discharge current (8/20 µs)
N-PE |
Imax |
10.00
kA |
Test voltage L-N |
Uoc |
10.0
kV |
Test voltage L-PE |
Uoc |
10.0
kV |
Test voltage N-PE |
Uoc |
10.0
kV |
Voltage protection level mode L-N |
Up |
1.30
kV |
Voltage protection level mode L-PE |
Up |
1.50
kV |
Voltage protection level mode N-PE |
Up |
1.50
kV |
Response time L-N |
ta |
25
ns |
Response time N-PE |
ta |
100
ns |
TOV 5 s L-N |
335
V |
|
TOV 5 s L-PE |
440
V |
|
TOV characteristic (TOV 5 s) |
withstand |
|
TOV 120 min L-N |
440
V |
|
TOV characteristic (120 min) |
withstand |
|
TOV 200 ms L-PE |
1
455 V |
|
TOV 200 ms N-PE |
1
200 V |
|
TOV characteristic (TOV 200 ms) |
safe
failure |
|
Cross-section of connected
conductors solid (max) |
2.50
mm2 |
|
Cross-section of connected
conductors stranded (max) |
1.50
mm2 |
|
Fault indication |
loss
of voltage, dark grey indication field |
|
Degree of protection |
IP
20 |
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
Humidity |
5
- 95 % |
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
ETIM Class |
EC000942 |
|
Customs tariff number |
85363030 |
|
EAN |
8595090560449 |
Dimensions:
Module of surge protection , 10 A, installation C High
Related Product
Module of surge protection , 10 A, installation C High
Fault signalling by supply interruption.Surge arrester especially for LED lights.Installation clo..
Module of surge ,6 A, installation C Low
Fault signalling by supply interruption.Surge protection especially for LED lights.Installation c..
Surge protection with RFI filter, 25 A
Visual fault signalling.Surge protection with integrated RFI filter.Installation to LV installatio..
Surge protection with RFI filter,16 A
Visual and remote fault signalling.Surge protection with integrated RFI filter.Installation to LV ..