/output cores,
fault signalling by supply interruption.
- Surge
arrester especially for LED lights.
- Installation
close to protected equipment in LV power circuits.
- Also for equipment in external part of building with high exposure level (according to IEEE C62.41.2).
Specifications:
|
Parameter name |
Parameter
value |
|
|
Type of SPD |
T2,T3 |
|
|
Nominal voltage |
Un |
230
V AC |
|
Maximum operating voltage |
Uc |
320.00
V AC |
|
Nominal load current |
IL |
10.000
A |
|
Type of network |
TT|TN |
|
|
Maximum overcurrent protection |
32
A gL/gG or C 32 A |
|
|
Short-circuit current rating |
ISCCR |
3.0
kA |
|
Residual current |
IPE |
0.004
mA |
|
Nominal discharge current (8/20 µs)
L-N |
In |
5.00
kA |
|
Nominal discharge current (8/20 µs)
N-PE |
In |
5.00
kA |
|
Maximum discharge current (8/20 µs)
L-N |
Imax |
10.00
kA |
|
Maximum discharge current (8/20 µs)
N-PE |
Imax |
10.00
kA |
|
Test voltage L-N |
Uoc |
10.0
kV |
|
Test voltage L-PE |
Uoc |
10.0
kV |
|
Test voltage N-PE |
Uoc |
10.0
kV |
|
Voltage protection level mode L-N |
Up |
1.30
kV |
|
Voltage protection level mode L-PE |
Up |
1.50
kV |
|
Voltage protection level mode N-PE |
Up |
1.50
kV |
|
Response time L-N |
ta |
25
ns |
|
Response time N-PE |
ta |
100
ns |
|
TOV 5 s L-N |
335
V |
|
|
TOV 5 s L-PE |
440
V |
|
|
TOV characteristic (TOV 5 s) |
withstand |
|
|
TOV 120 min L-N |
440
V |
|
|
TOV characteristic (120 min) |
withstand |
|
|
TOV 200 ms L-PE |
1
455 V |
|
|
TOV 200 ms N-PE |
1
200 V |
|
|
TOV characteristic (TOV 200 ms) |
safe
failure |
|
|
Fault indication |
loss
of voltage, dark grey indication field |
|
|
Degree of protection |
IP
20 |
|
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
|
Humidity |
5
- 95 % |
|
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
|
ETIM Class |
EC000942 |
|
|
Customs tariff number |
85363030 |
|
|
EAN |
8595090562450 |
Dimensions:
Datasheet:
Module of surge protection, input/output cores, 10 A
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: SP-T2+T3-320/Y-CCC-LED
- MPN: SP-T2+T3-320/Y-CCC-LED
Terms & Conditions
All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..