• Module with surge protection for additional installation, acoustic fault signalling.

Acoustic fault signalling.

  • SPD for additional installation to devices or equipments.
  • Installation to LV installations, close to protected equipment.
  • For protection of all LV equipments against surge voltage.
  • Non-symetrical connection.

Specifications:


Parameter name

Parameter value

Type of SPD

T3

Mounting

installation box

Nominal voltage

Un

230 V AC

Maximum operating voltage L-N

Uc

275.00 V AC

Maximum operating voltage N-PE

Uc

255.00 V AC

Type of network

TN|TT

Maximum overcurrent protection

B 16 A

Short-circuit current rating

ISCCR

1.5 kA

Nominal discharge current (8/20 µs) L-N

In

3.00 kA

Nominal discharge current (8/20 µs) N-PE

In

6.00 kA

Test voltage L-N

Uoc

6.0 kV

Test voltage N-PE

Uoc

12.0 kV

Voltage protection level mode L-N

Up

1.45 kV

Voltage protection level mode N-PE

Up

1.50 kV

Response time L-N

ta

25 ns

Response time N-PE

ta

100 ns

TOV 5 s L-N

335 V

TOV 5 s L-PE

440 V

TOV characteristic (TOV 5 s)

withstand

TOV 120 min L-N

440 V

TOV characteristic (120 min)

withstand

TOV 200 ms L-PE

1 455 V

TOV 200 ms N-PE

1 200 V

TOV characteristic (TOV 200 ms)

safe failure

Fault indication

acoustic signalling

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-20 / 70 °C

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC000942

Customs tariff number

85363010

EAN

8595090567370



Dimensions:


















Write a review

Note: HTML is not translated!
Captcha

Module with surge protection for additional installation, acoustic fault signalling.

0 reviews / Write a review

* Required fields



Related Product

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..

Replacement module for SLP-PV500 V/U.

Replacement module for SLP-PV500 V/U.

Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..