• 500m Twisted Pair Control Signal Cable 2 Pair Shielded Grey.

Construction

Conductor

Stranded Electrolytic Annealed Copper Wire (IEC 60228 /VDE 0295 / HD 383 / BS6360 Class 2)

Insulation

PE (EN 50290-2 / VDE 0207-2YI1)

Color Coding

Acc. to DIN 47100

Lay-up

Pairs are twisted in layers

Separator

Polyester tape

Overall Shielding

AL-PES tape (with 7x0.30 mm tinned copper drain wire)

Outer Sheath

PVC (HD 21.1.S4 / VDE 0281 TM1), Grey (Ral 7001)

Cable Diameter

6.6 mm


Electrical and Technical Properties

Operating Voltage

300/500 V

Test Voltage

1500 V

Insulation Resistance

 > 5000 MΩ . km

Temperature Range

Fixed -40° C · · · +70° C

During Installation -5 °C ........+50 °C

Min. Bending Radius

Static : 7.5 x Cable Diameter

Flexing : 15 x Cable Diameter

Flame Tests

IEC 60332-1, VDE 0482-265-2-1

Write a review

Note: HTML is not translated!
Captcha

500m Twisted Pair Control Signal Cable 2 Pair Shielded Grey.

0 reviews / Write a review

  • AED2.72

* Required fields



Related Product

Surge protection for 2-core floating signalling networks, 48 V DC, max. 0.5 A

Surge protection for 2-core floating signalling networks, 48 V DC, max. 0.5 A

Coupling impedance (resistance), screw terminals.Coarse and fine surge protection for 2-core signall..

Cable Pulling Grip With Two Eyes 50 - 60mm L1250mm Open.

Cable Pulling Grip With Two Eyes 50 - 60mm L1250mm Open.

With two eyes and thimble, laterally open, including two closing wires, total length 1450 mm, worki..

Cable Trough -42U -100mm Wide Black Webb.

Cable Trough -42U -100mm Wide Black Webb.

Webb vertical cable manager provides a neat and clean means of organizing cables in the rack system..

Disc Caulking 4 (used with Gland Caulking 3)

Disc Caulking 4 (used with Gland Caulking 3)

Used with Gland Caulking 3 and Compound 16A.Each Gland requires 2 discs...