• DL-Cat. 5e 16 RACK PANEL

Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.

Technical specifications

Type of SPD

 

C2,C3

Location of SPD 

 

ST 3

Maximum operating voltage 

Uc

6V DC and 8V DC

Nominal load current

IL

0,100A

C2 nominal discharge current (8/20 µs) per core

In

0,20kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

1,60kA

C2 voltage protection level mode core-core at In 

Up

40V

C2 voltage protection level mode core-PE at In 

Up

350V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

65V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-core 

ta

100ns

Insertion attenuation at 250 MHz 

 

1,20dB

Connection (input - output)

 

RJ 45/RJ 45

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

60 °C

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC000943

Write a review

Note: HTML is not translated!
Captcha

DL-Cat. 5e 16 RACK PANEL

0 reviews / Write a review

* Required fields



Related Product

Cable Control 4C 1sq Mm LIYY/18AWG UNSCN - 305m/Roll

Cable Control 4C 1sq Mm LIYY/18AWG UNSCN - 305m/Roll

ApplicationsThese PVC cables are used in industrial applications for signal transmission. They can b..

Compact Rack Lamp

Compact Rack Lamp

FeaturesWith magnetic mountingEnergy-saving lampProtective contact socketOn/off switch3 m power supp..

Base Assembly With Cable Entry W800 D1000 Miracel

Base Assembly With Cable Entry W800 D1000 Miracel

For covering the rack undersideWith rubber sealing for flexible cable entry on the front and rearPro..

Galvanised cable entrance device

Galvanised cable entrance device

SpecificationPart NumberkgJZ-KEG06051mm2,5JZ-KEG08076mm3,5JZ-KEG10089mm4,2JZ-KEG120114mm5,0JZ-KEG140..