Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the
boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.
Technical specifications
Type of SPD | C2,C3 | |
Location of SPD | ST 3 | |
Maximum operating voltage | Uc | 6V DC and 8V DC |
Nominal load current | IL | 0,100A |
C2 nominal discharge current (8/20 µs) per core | In | 0,20kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 1,60kA |
C2 voltage protection level mode core-core at In | Up | 40V |
C2 voltage protection level mode core-PE at In | Up | 350V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 65V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-core | ta | 100ns |
Insertion attenuation at 250 MHz | 1,50dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 60 °C | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC000943 |
DL-Cat. 5e 8 RACK PANEL
Related Product
Surge protection for small-voltage AC/DC power supply networks with RFi filter, up to 48 V AC or DC
Visual fault singallingSurge protection with integrated RFi filter.Installation to LV installations,..
Compact Rack Lamp
FeaturesWith magnetic mountingEnergy-saving lampProtective contact socketOn/off switch3 m power supp..
Distribution Box Int 100pr 301A Empty 160x210x121
T70-2206 (Unloaded) require disconnection strips (T70-2203).100 PAIR CONNECTION&..
AED 85.00
Combination of lightning current and surge arrester for one-phase aplications , 25 Ka
Pluggable module, visual fault signalling, and remote fault signalling.A combination of a three-pole..