Protection of line and communication interfaces of the PROFIBUS industrial bus-bar system. Coarse and fine surge protection. Also, cable shielding is protected.
Parameters
Type of SPD | C2,C3 | |
Connection (input - output) | terminals-terminals | |
Location of SPD | ST 2+3 | |
Nominal voltage | Un | 5V DC |
Maximum operating voltage | Uc | 6V AC |
Maximum operating voltage | Uc | 8V AC |
Nominal load current | IL | 0,060 A |
C2 nominal discharge current (8/20 µs) core-core | In | 10,00Ka |
C2 voltage protection level mode core-core at In | Up | 150 V |
C2 voltage protection level mode core-COM at In | Up | 150 V |
C2 voltage protection level mode COM-PE at In | Up | 350 V |
C2 voltage protection level mode SH-PE at In | Up | 350 V |
C3 voltage protection level mode core-core at 1 kV/µ | Up | 40 V |
C3 voltage protection level mode core-COM at 1 kV/µs | Up | 40 V |
C3 voltage protection level mode COM-PE at 1 kV/µs | Up | 650 V |
C3 voltage protection level mode SH-PE at 1 kV/µs | Up | 650 V |
Response time core-core | ta | 1 ns |
Response time core COM |
| 1 ns |
Response time COM-PE | ta | 100ns |
Response time SH-PE | ta | 100ns |
Serial resistance per core | R | 1,00Ω |
Treshold frequency core-core | f | 100,00MHz |
Cross-section of connected conductors solid - max |
| 400 mm2 |
Cross-section of connected conductors stranded - max |
| 2,50 mm2 |
Degree of protection |
|
DM-PROFIBUS 5 VRelated ProductGalvanised cable and rope entrance deviceSpecificationPart NumberkgJZKSE101a76mm420mm16,5JZKSE101b90mm420mm17,0JZKSE101c101mm420mm17,5JZKSE10.. Cable Tray 42U Zinc Plated W=200MM.42U Cable Tray Zinc Plated W=200mm Multi Slotted version.Features: Width: 200 .. 2,5 mm2 3 slots cross-connectorSPD - for data, signalling and telecommunications lines / I&C / Accesories for I&CCross conn.. Power Cord IEC Lock PLUS 3x1.0mmsq C13 TO C14 10A 2m BlackIEC Lock + Power Extension C13-C14 with unique built in with Easy Release System IEC Locking C13 Con.. AED 32.00 |





-100x100.jpg)