Protection of line and communication interfaces of the PROFIBUS industrial bus-bar system. Coarse and fine surge protection. Also, cable shielding is protected.
Parameters
Type of SPD | C2,C3 | |
Connection (input - output) | terminals-terminals | |
Location of SPD | ST 2+3 | |
Nominal voltage | Un | 24V DC |
Maximum operating voltage | Uc | 21V AC |
Maximum operating voltage | Uc | 29V AC |
Nominal load current | IL | 0,060 A |
C2 nominal discharge current (8/20 µs) core-core | In | 10,00Ka |
C2 voltage protection level mode core-core at In | Up | 300 V |
C2 voltage protection level mode core-COM at In | Up | 300 V |
C2 voltage protection level mode COM-PE at In | Up | 350 V |
C2 voltage protection level mode SH-PE at In | Up | 350 V |
C3 voltage protection level mode core-core at 1 kV/µ | Up | 40 V |
C3 voltage protection level mode core-COM at 1 kV/µs | Up | 40 V |
C3 voltage protection level mode COM-PE at 1 kV/µs | Up | 650 V |
C3 voltage protection level mode SH-PE at 1 kV/µs | Up | 650 V |
Response time core-core | ta | 1 ns |
Response time core COM |
| 1 ns |
Response time COM-PE | ta | 100ns |
Response time SH-PE | ta | 100ns |
Serial resistance per core | R | 1,00Ω |
Treshold frequency core-core | f | 100,00MHz |
Cross-section of connected conductors solid - max |
| 400 mm2 |
Cross-section of connected conductors stranded - max |
| 2,50 mm2 |
Degree of protection |
|
24V Data Interface Surge Protection For Industrial Bus
Terms & Conditions
Related ProductLocking IEC C14 To C13 Power Cord 3Ft 10A 250V.IEC 320 C14 Plug to IEC 320 C13 Connector WS-Lock 0.9 Meters / 3 Feet 10a/250v H05VV-F3G1.0 & 17.. Desk with right office pedestal(150 + 300 mm),depth 670 mm(CRS).Basic desk: Basic desk with 4 legs.Model:With lockable office pedestal, left.Drawer height, 1 x 150 .. Supply cable for Knürr-DICON unit (2.0 m).Specification:Network plug CEE/VII - GST 18 socket (Wieland). Line H05VV-F3G 1.5 mm2. Color: White.. Lightning current arrester replacement module, for four 1-core signalling lines, 12 V DC, max. 1 APluggable module, coupling impedance (R – resistance), line separated from protective earth via GDT... |