vCombination of coarse and fine protection of data and M&C lines. For LSA separating strips.
Technical specifications
Type of SPD | | C3,C2 |
Connection (input - output) | | LSA disconnection rail |
Accessories | | grounding rail |
Location of SPD | | ST 2+3 |
Maximum operating voltage | Un | 11V AC |
Maximum operating voltage | Uc | 16V DC |
Nominal load current | IL | 0,500A |
C2 nominal discharge current (8/20 µs) per core ` | In | 500kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10,00kA |
C2 voltage protection level mode core-PE at In | Up | 400V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 21V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-PE | ta | 100ns |
Serial resistance per core | R | 1,60Ω |
Treshold frequency core-core | f | 2,50MHz |
Degree of protection | | IP 20 |
Range of operating temperatures - min | | -40 °C |
Range of operating temperatures - max | | -70 °C |
ETIM Class | EC001625 | |
Mounting | | LSA disconnection rail |
According to standard | | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 |
CLSA-12
Related Product
Cable Control 2C 2.5sqmm LIHH UNSCN LSO Sheathed -305m/Roll
LIHH cables are used in the industrial applications for indoor use for signal transmission. These ca..
Power Cord And Guard For Single Fan
Power Cord And Guard For Single Fan...
2 Core Shielded Control Cable 1mm² 305m Roll for Automation.
ApplicationsThese shielded and PVC insulated cables are used as signal transmission cables in indust..
AED2.19
FO Patch Cord 62.5/125 Dpx OM1 2.0mm LC/UPC-SC/UPC-3m LSOH
Fiber patch cord for interconnect application is designed for use in data communication, process con..