vCombination of coarse and fine protection of data and M&C lines. For LSA separating strips.
Technical specifications
Type of SPD | | C3,C2 |
Connection (input - output) | | LSA disconnection rail |
Accessories | | grounding rail |
Location of SPD | | ST 2+3 |
Maximum operating voltage | Un | 11V AC |
Maximum operating voltage | Uc | 16V DC |
Nominal load current | IL | 0,500A |
C2 nominal discharge current (8/20 µs) per core ` | In | 500kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10,00kA |
C2 voltage protection level mode core-PE at In | Up | 400V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 21V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-PE | ta | 100ns |
Serial resistance per core | R | 1,60Ω |
Treshold frequency core-core | f | 2,50MHz |
Degree of protection | | IP 20 |
Range of operating temperatures - min | | -40 °C |
Range of operating temperatures - max | | -70 °C |
ETIM Class | EC001625 | |
Mounting | | LSA disconnection rail |
According to standard | | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 |