• CLSA-12

vCombination of coarse and fine protection of data and M&C lines. For LSA separating strips.

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

11V AC

Maximum operating voltage 

Uc

16V DC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

400V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

21V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

2,50MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

-70 °C

ETIM Class 

 

EC001625

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

Write a review

Note: HTML is not translated!
Captcha

CLSA-12

0 reviews / Write a review

* Required fields



Related Product

Cable In/Out FO 6C 9/125 CLT DIEL

Cable In/Out FO 6C 9/125 CLT DIEL

1. Optical fibre : Multimode or singlemode (FOTAG color code)2. Tube : Thermopla..

AED 3.40

Cable 4C, 18AWG, US, PVC, R40049-1A - 305m/Roll

Cable 4C, 18AWG, US, PVC, R40049-1A - 305m/Roll

4/C 18 AWG COMMERCIAL AUDIO AND GENERAL PURPOSE LOW VOLTAGE POWER LIMITED CABLE 60C 300VRISER RATED&..

AED 984.25

Stripper Universal

Stripper Universal

For  wire (UTP/STP) or  wire and multi conductor cable from 3.2 mm-9 mm max.Irre..

AED 32.76

Standard Socket Power Cords

Standard Socket Power Cords

NEMA 5-20P to IEC 60320 C19, 20A, 125V..