• CLSA-HF6

Combination of coarse and fine protection designed to protect data lines with high speed rates

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

6V AC

Maximum operating voltage 

Uc

9V AC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

350V

C2 voltage protection level mode core-core at In 

Up

32V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

15V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

55,00MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

70 °C

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001625


Write a review

Note: HTML is not translated!
Captcha

CLSA-HF6

0 reviews / Write a review

* Required fields



Related Product

Bracket Cable Bearer No.3: 115mm

Bracket Cable Bearer No.3: 115mm

Cable bracket and bearerManufactured from galvanised mild steel to BS EN ISO 1461 : 1999Mounted to t..

Jumper Tie Bar Miracel 45U 2/set - RAL7032

Jumper Tie Bar Miracel 45U 2/set - RAL7032

Jumper Tie Bar Miracel 45U 2/set - RAL7032..

LDD Optical Cable for Mobile and Tactical use

LDD Optical Cable for Mobile and Tactical use

This specification covers optical cables with 2 or 4 fibers. LDD tactical cable is equipped with two..

Galvanised cable protector with roller

Galvanised cable protector with roller

SpecificationPart NumberkgJZ-KET06051mm4,0JZ-KET07561mm4,2JZ-KET08076mm4,5JZ-KET10089mm5,0JZ-KET1201..