• CLSA-HF6

Combination of coarse and fine protection designed to protect data lines with high speed rates

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

6V AC

Maximum operating voltage 

Uc

9V AC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

350V

C2 voltage protection level mode core-core at In 

Up

32V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

15V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

55,00MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

70 °C

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001625


Write a review

Note: HTML is not translated!
Captcha

CLSA-HF6

0 reviews / Write a review

* Required fields



Related Product

FO Patch Panel 24P SC Simplex Unloaded Webb

FO Patch Panel 24P SC Simplex Unloaded Webb

Features24 ports single structure fibre patch panel19” installation, glide-out category4 cable entri..

SPECIAL COMPONENTS

SPECIAL COMPONENTS

Gel lubricant VOLTALUB-JETW supplied in bottle/bucket pack, reduces up to 80% the friction effect du..

PDU 12Way Vertical Filtered - RAL7021

PDU 12Way Vertical Filtered - RAL7021

A high quality range of horizontal and vertical power distribution units with angled sockets (vertic..

AED 150.00

DL-Cat. 5e 16 RACK PANEL

DL-Cat. 5e 16 RACK PANEL

Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installat..