• CLSA-HF6

Combination of coarse and fine protection designed to protect data lines with high speed rates

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

6V AC

Maximum operating voltage 

Uc

9V AC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

350V

C2 voltage protection level mode core-core at In 

Up

32V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

15V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

55,00MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

70 °C

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001625


Write a review

Note: HTML is not translated!
    Bad           Good
Captcha

CLSA-HF6

* Required fields


Related Product

PDU 4Way Left Angled Vertical Unswitched

PDU 4Way Left Angled Vertical Unswitched

XAL - Vertical Rack Mount Angled Left16 Amps total loadSupplied with 3mtrs flex to 13A UK fused plug..

223.00AED

Telescopic mast roller made of light alloy ø 460mm

Telescopic mast roller made of light alloy ø 460mm

Specification<-->kg1180-2200 mm17,5..

Handset Coiled Cord 7ft Black

Handset Coiled Cord 7ft Black

Handset Coiled Cord 7ft Black..

Mountpost 23U Miracel Steel (2/Set)

Mountpost 23U Miracel Steel (2/Set)

 For front and rear installation in the rackCaged nut mountable in HU increments(19”)Please als..