Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.
Technical specifications
Type of SPD | C2,C3 | |
Location of SPD | ST 3 | |
Maximum operating voltage | Uc | 6V DC and 8V DC |
Nominal load current | IL | 0,100A |
C2 nominal discharge current (8/20 µs) per core | In | 0,20kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 1,60kA |
C2 voltage protection level mode core-core at In | Up | 40V |
C2 voltage protection level mode core-PE at In | Up | 350V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 65V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-core | ta | 100ns |
Insertion attenuation at 250 MHz | 1,20dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 60 °C | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC000943 |
DL-Cat. 5e 16 RACK PANEL
Related Product
Lightning current arrester for 2/3-core signalling lines, 230 V DC, max. 0.5 A
Pluggable module, coupling impedance (R – resistance), line separated from protective earth via GDT..
Worktops, 90° wall right, D1050 straight (W- 1230).
Premium worktops made from quality 3-layer particle board with a durable HPL-coating. 30mm strong ..
Knürr DI-STRIP® Compact(D Schuko -8, L-483).
Specification:Optionally with illuminated switch; 2-pole switching. 19" installation option (for l..
Separating inductor (bridge) for coordination of SPDs, up to 32 A.
Coupling impedance.For coordination of SPDs type 1 and 2 or type 2 and 4.Specifications: ..