Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the
boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.
Technical specifications
Type of SPD | C2,C3 | |
Location of SPD | ST 3 | |
Maximum operating voltage | Uc | 6V DC and 8V DC |
Nominal load current | IL | 0,100A |
C2 nominal discharge current (8/20 µs) per core | In | 0,20kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 1,60kA |
C2 voltage protection level mode core-core at In | Up | 40V |
C2 voltage protection level mode core-PE at In | Up | 350V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 65V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-core | ta | 100ns |
Insertion attenuation at 250 MHz | 1,50dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 60 °C | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC000943 |
DL-Cat. 5e 8 RACK PANEL
Related Product
Jensen Tools G1766JTR Pallet #10, Empty. 15 x 10.75"
Pallet Size: 15 x 10.75"No. 1: 10..
Bench Mounting Kit For Use With MicroCare Solvents
The MicroCare MCC-BK3 Bench Mounting Kit is designed for use with the Solvent Miser Trigger Grip sys..
AED 58.00
Cable Trough 41U - RAL7021 (N)
ertical Cable Management for 41U Cabinet For orderly cable management in the MIRACEL..
Cable Drum - RBD-200
Mobile drum, with strap belts for shoulder wear. Suitable for use in the field.Weight with HMA conne..