• CLSA-6

Product Description

Combination of coarse and fine protection of data and M&C lines. For LSA separating strips.

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

6V AC

Maximum operating voltage 

Uc

9V AC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

400V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

13V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

1,50MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

-70 °C

ETIM Class 

 

EC001625

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

 

Write a review

Note: HTML is not translated!
Captcha

CLSA-6

0 reviews / Write a review

* Required fields



Related Product

Cable guiding device for manholes with 4 protection rollers

Cable guiding device for manholes with 4 protection rollers

Specificationø 60 mm3 Kg400 x 400 x 80 mm..

SAM Open storage bins

SAM Open storage bins

Material- Polyethylene..

Patch Cord Booted CAT5E 1m - Blue - Fusion

Patch Cord Booted CAT5E 1m - Blue - Fusion

High quality Cat 5e UTP Patch Lead Wired 258A (T568B) 50 Micron Gold Plated RJ45 connectors. Each le..

AED 2.91

Side Panel 41U W1000 Miracel - RAL7035

Side Panel 41U W1000 Miracel - RAL7035

Protection ratingWith installation in the Miracel rack (depending on the other rack components), a m..