two-stage protection of Ethernet, instalation at the entrance of th line into the stucture and close to equipment,
at the boundary of LPZ 0 and LPZ 1 or higher, for protection of Ethernet network Cat. 6 against surge over voltage
Technical specifications
Type of SPD | | D1,C2,C3 |
Location of SPD | | ST 1+2+3 |
Maximum operating voltage | Uc | 9V DC |
Nominal load current | IL | 0,500A |
C2 nominal discharge current (8/20 µs) per core ` | In | 0,15kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10,00kA |
D1 total discharge current (10/350 µs) cores-PE | ITotal | 2,00kA |
C2 voltage protection level mode core-core at In | Up | 50V |
C2 voltage protection level mode core-PE at In | Up | 400V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 20V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-PE | ta | 100ns |
Insertion attenuation at 250 MHz | 1,50dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | | IP 20 |
Range of operating temperatures - min | | -40 °C |
Range of operating temperatures - max | | 80 °C |
ETIM Class | EC000943 | |
According to standard | | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 |
DL-1G-RJ45-5V
Related Product
Knürr Elicon® VC Working Surfaces Linear (W- 1800, H- 900).
Specification:Single table or linked. Height-selectable in 20 mm increments from 640 to 760 mm. On..
Cabinet 32U 600x800 Perf Front Glass Door, Rear Perf Door
Inorax-ST, a cost effective network rack cabinet system fulfills high density cabling and data cente..
دإ Dhs3,465.00
Basic CB-12V2 16-20A/30A (12) C13/NEMA 5-20R
The Sentry Basic Cabinet Power Distribution Unit product family provides a simple solution where rel..
دإ Dhs610.00
FO Patch Cord 50/125 Dpx OM3 2.0mm SC/UPC-SC/UPC-5m LSOH.
Webb’s fibre optic patch cords are manufactured from high-quality optical fibre, terminated with s..