•  FX-090 B75 T F/F
BNC connectors
Protection for coaxial lines. Installation at the boundary of LPZ 0 and LPZ 1 zones at the line input into the
building. Suitable as the 1st level of surge protection in coordination with the SX type.

Parameters

 

Type of SPD 

 

D1,C2

Location of SPD 

 

ST 1

Maximum operating voltage

Uc

70 V DC

Nominal load current 

IL

4,000 A

C2 nominal discharge current (8/20 µs) core-SH 

In

10,00KA

C2 nominal discharge current (8/20 µs) SH-PE 

In

10,00KA

D1 impulse discharge current (10/350 µs) core-SH 

Iimp

2,50kA

D1 impulse discharge current (10/350 µs) core-PE

Iimp

2,50kA

C3 voltage protection level mode core-SH at 1 kV/µs

Up

600v

C3 voltage protection level mode SH-PE at 1 kV/µs 

Up

600v

Wave impedance 

Z

75Ω

Insertion attenuation 

 

0,60 dB

SWR 

 

1,2

Bandwidth - min

f

0,00MHZ

Bandwidth - max 

f

2150,00MHz

Response time core-SH 

ta

100ns

Response time SH-PE 

ta

100ns

Connection (input - output) 

 

BNC 75

Degree of protection

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

-80 °C

Mounting

 

DIN rail 35 mm

According to standard 

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001466

Write a review

Note: HTML is not translated!
Captcha

FX-090 B75 T F/F

0 reviews / Write a review

* Required fields



Related Product

Galvanised cable protector with roller

Galvanised cable protector with roller

Specificationkg133mm7,0..

VOLTAFIX • ø 7,5 mm

VOLTAFIX • ø 7,5 mm

DescriptionReviews (0)Fiberglass Rod VOLTAFIX ø 7,5 mm with Polypropylene outer coating comes spoole..

Bracket Cable Bearer No.3: 115mm

Bracket Cable Bearer No.3: 115mm

Cable bracket and bearerManufactured from galvanised mild steel to BS EN ISO 1461 : 1999Mounted to t..

ERGOCON WorkStation _ Control Room Console _ KVM-ready Technology Cabinet _ W2200 D1100 _ Curved

ERGOCON WorkStation _ Control Room Console _ KVM-ready Technology Cabinet _ W2200 D1100 _ Curved

KVM-ready Technology Cabinet :- Up to 3x6 RU for integrating technology, typical for KVM application..