• Lightning current arrester replacement module, for up to 4-core shielding floating signalling line, 6 V DC, max. 1 A

Pluggable module, coupling impedance (R – resistance), line separated from protective earth via GDT

  • Lightning current arrester with coarse and fine surge protection for up to 4-core signalling lines
  • Installation at the boundary of LPZ 0 and LPZ 1 zones or higher, at the line entry into building and also installation close to protected device
  • For protection of communication interfaces of I&C, MaR systems, electronic security and fire detection systems, etc. (mainly for RS-485 inter- faces) against impact of surge voltage
  • Coarse and fine surge protection (core – core) in differential mode and coarse surge protection in common mode (line – PE)


Specifications:


Parameter name

Parameter value

Type of SPD

D1,C2

Location of SPD

ST 1+2+3

Mounting

DIN rail 35 mm

Nominal voltage

Un

6 V DC

Maximum operating voltage

Uc

6.00 V AC

Maximum operating voltage

Uc

8.50 V DC

Nominal load current

IL

1.000 A

Treshold frequency core-core

f

1.20 MHz

Serial resistance per core

R

0.80 Ω

D1 impulse discharge current (10/350 µs) per core

Iimp

2.50 kA

D1 total discharge current (10/350 µs) cores-PE

ITotal

5.00 kA

C2 nominal discharge current (8/20 µs) GND-PE

In

10.00 kA

C2 nominal discharge current (8/20 µs) per core

In

10.00 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

20.00 kA

C3 nominal discharge current (10/1000 µs) core-PE

ISM

10 A

C3 nominal discharge current (10/1000 µs) core-core

ISM

10 A

C3 voltage protection level mode GND-PE at 1 kV/µs

Up

550.00 V

C3 voltage protection level mode core-GND at 1 kV/µs

Up

550.00 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

18 V

Response time core-core

ta

1 ns

Response time core-GND

ta

100 ns

Response time GND-PE

ta

100 ns

Connection (input - output)

terminals-terminals

Cross-section of connected conductors solid (min)

0.14 mm2

Cross-section of connected conductors solid (max)

4.00 mm2

Cross-section of connected conductors stranded (min)

0.14 mm2

Cross-section of connected conductors stranded (max)

2.50 mm2

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 70 °C

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001625

Plug module

BDG-006-V/1-4-0

Customs tariff number

85363010

EAN

8595090564676


Dimensions:




Replacement module: BDG-006-V/1-4-0

Write a review

Note: HTML is not translated!
Captcha

Lightning current arrester replacement module, for up to 4-core shielding floating signalling line, 6 V DC, max. 1 A

0 reviews / Write a review

* Required fields



Related Product

Two-stage surge protection, LPZ0 and higher

Two-stage surge protection, LPZ0 and higher

RJ45 sockets.Combination of coarse and fine protection of Ethernet line with PoE.Instalation at th..

Two-stage surge protection, LPZ0 and higher

Two-stage surge protection, LPZ0 and higher

RJ45 sockets.Combination of coarse and fine protection of Ethernet line with PoE.Instalation at th..

Two-stage surge protection for outdoor Ethernet devices with PoE

Two-stage surge protection for outdoor Ethernet devices with PoE

Surge protection for outdoor Ethernet devices with PoE.Two-stage Ethernet surge protection in comb..

 Surge protection for ISDN telecommunication line, RJ45 sockets

Surge protection for ISDN telecommunication line, RJ45 sockets

RJ45 socketsCombination of coarse and fine protection for ISDN lines.For protection of one pair o..