• Coarse single stage surge arrester – Gas Discharge Tube, screw terminal, 180 V DC

B – Gas Discharge Tube, screw terminal

  • Coarse single stage surge arrester
  • For protection of signaling, data and other lines against impact of surge voltage
  • Usable mainly for the separation of shielding from the protective earth


Specifications:

Parameter name

Parameter value

Type of SPD

C2

Location of SPD

ST 2

Mounting

DIN rail 35 mm

Maximum operating voltage

Uc

127.00 V AC

Maximum operating voltage

Uc

180.00 V DC

Nominal load current

IL

16.000 A

C2 nominal discharge current (8/20 µs) per core

In

10.00 kA

C3 voltage protection level mode core-PE at 1 kV/µs

Up

600 V

Response time core-PE

ta

100 ns

Connection (input - output)

terminals-terminals

Cross-section of connected conductors solid (max)

4.00 mm2

Cross-section of connected conductors stranded (max)

2.50 mm2

Range of ambient temperatures (min/max)

-40 / 70 °C

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC000943

Customs tariff number

85363010

EAN

8595090551492


Dimensions:


Write a review

Note: HTML is not translated!
Captcha

Coarse single stage surge arrester – Gas Discharge Tube, screw terminal, 180 V DC

0 reviews / Write a review

* Required fields



Related Product

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Spark gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 3+1 mode.Installa..

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

park gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 1+1 mode.Installat..

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of v..

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking.Combination of varistor lightning current ..