• Surge protection for Ethernet without PoE, Cat.6A, LPZ1 and higher

RJ45 sockets1.

  • Fine surge protection of Ethernet line.
  • Installation close to protected equipment.
  • For protection of Ethernet line Cat. 6A against surge voltage.
  • In the scope of delivery: universal plastic adapter for mounting on DIN rail and GND 2 holder.


Specifications:

Parameter name

Parameter value

Type of SPD

C2,C3

Location of SPD

ST 2+3

Mounting

DIN rail 35 mm

Maximum operating voltage

Uc

6.00 V AC

Maximum operating voltage

Uc

8.50 V DC

Maximum operating voltage POE

Uc

6.00 V AC

Maximum operating voltage POE

Uc

8.50 V DC

Nominal load current per core at 25 °C

IL

0.5 A

Treshold frequency core-core

f

500.00 MHz

Insertion attenuation at treshhold frequency

2.90 dB

C2 nominal discharge current (8/20 µs) per core

In

0.20 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

1.60 kA

C2 voltage protection level mode (POE) at In

Up

55.00 V

C2 voltage protection level mode core-PE at In

Up

400 V

C2 voltage protection level mode core-core at In

Up

55 V

C3 voltage protection level mode (POE) at 1 kV/µs

30.00 V

C3 voltage protection level mode core-PE at 1 kV/µs

Up

600 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

30 V

Response time core-core

ta

1 ns

Response time core-PE

ta

100 ns

Connection (input - output)

RJ45/RJ45

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC000943

Customs tariff number

85363030

EAN

8595090565741


Dimensions:



Write a review

Note: HTML is not translated!
Captcha

Surge protection for Ethernet without PoE, Cat.6A, LPZ1 and higher

0 reviews / Write a review

* Required fields



Related Product

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Spark gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 3+1 mode.Installa..

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

park gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 1+1 mode.Installat..

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of v..

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking.Combination of varistor lightning current ..