RJ45 sockets, PCB, with injector.
- Combination of coarse and fine protection of
Ethernet line with PoE.
- Instalation at the entry of the line into
building and close to protected equipment, at the boundary of LPZ 0 and LPZ 1
or higher.
- For protection of Ethernet line Cat. 6 or
Cat. 6A with PoE (Power over Ethernet) in mode A or B against surge voltage.
- For assembly to DL-CS-RACK-1U-INJECTOR.
Specifications:
Parameter name |
Parameter value |
|
Type
of SPD |
D1,C2,C3 |
|
Location
of SPD |
ST 1+2+3 |
|
Mounting |
DL-CS-RACK-1U-INJECTOR |
|
Maximum
operating voltage |
Uc |
8.50 V DC |
Maximum
operating voltage POE |
Uc |
58.00 V DC |
Nominal
load current per core at 25 °C |
IL |
0.5 A |
Treshold
frequency core-core |
f |
250.00 MHz |
Insertion
attenuation at treshhold frequency |
1.20 dB |
|
D1
total discharge current (10/350 µs) cores-PE |
ITotal |
2.00 kA |
C2
nominal discharge current (8/20 µs) per core |
In |
0.15 kA |
C2
total discharge current (8/20 µs) cores-PE |
ITotal |
10.00 kA |
C2
voltage protection level mode core-PE at In = 1,25 kA |
Up |
700.00 V |
C2
voltage protection level mode core-core at In |
Up |
70 V |
C3
voltage protection level mode (POE) at 1 kV/µs |
80.00 V |
|
C2
voltage protection level mode (POE) at In = 1,25 kA |
Uc |
90.00 V |
C3
voltage protection level mode core-PE at 1 kV/µs |
Up |
500 V |
C3
voltage protection level mode core-core at 1 kV/µs |
Up |
80 V |
Response
time core-core |
ta |
1 ns |
Response
time core-PE |
ta |
100 ns |
Connection
(input - output) |
RJ 45/RJ 45 |
|
Degree
of protection |
IP 20 |
|
Range
of ambient temperatures (min/max) |
-40 / 80 °C |
|
Humidity |
5 - 95 % |
|
According
to standard |
EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 |
|
Customs
tariff number |
85363030 |
|
EAN |
8595090565703 |
Dimensions:
Surge protection for Ethernet 1 Gbit/s (Cat. 6) or 10 Gbit/s (Cat. 6A), 2 kA (10/350 µs).
Related Product
Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)
Spark gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 3+1 mode.Installa..
Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)
park gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 1+1 mode.Installat..
Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of v..
Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking.Combination of varistor lightning current ..