• Combination of lightning , TN-S, 100 kA (10/350 µs), 240 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.

  • Four-pole high performance lightning current arrester.
  • Installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards.
  • For protection against impact of direct or indirect lightning strikes in wide range of applications – houses, office or industrial buildings, resp. to sub-distribution boards in large buildings.


Specifications:


Parameter name

Parameter value

Type of SPD

T1,T2

Mounting

DIN rail 35 mm

Nominal voltage

Un

230 V AC

Maximum operating voltage

Uc

260.00 V AC

Nominal load current for "V" connection

IL

125 A

Type of network

TN-S

Maximum overcurrent protection

250 A gL/gG

Maximum overcurrent protection for "V" connection

125 A gL/gG

Short-circuit current rating

ISCCR

50.0 kA

Total discharge current (10/350 µs)

ITotal(10/350)

100.00 kA

Lightning impulse current (10/350 µs)

Iimp

25.00 kA

Nominal discharge current (8/20 µs)

In

30.00 kA

Maximum discharge current (8/20 µs)

Imax

60.00 kA

Voltage protection level

Up

1.50 kV

Residual voltage of MOV at In

URES

0.85 kV

Response time

ta

100 ns

TOV 5 s L-N

335 V

TOV characteristic (TOV 5 s)

withstand

TOV 120 min L-N

440 V

TOV characteristic (120 min)

withstand

Cross-section of connected conductors solid (min)

2.50 mm2

Cross-section of connected conductors solid (max)

50.00 mm2

Cross-section of connected conductors stranded (min)

2.50 mm2

Cross-section of connected conductors stranded (max)

35.00 mm2

Cross-section of remote indication conductors solid (max)

1.5 mm2

Cross-section of remote indication conductors stranded (max)

1.5 mm2

Fault indication

red indication field

Remote indication

potential-free change-over contact

Remote indication contacts

250V/0,5A AC,250V/0,1A DC

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC001457

Plug module

FLP-B+C MAXI V/0

Customs tariff number

85363090

EAN

8595090535713



Dimensions:






Replacement module: FLP-B+C MAXI V/0





Write a review

Note: HTML is not translated!
Captcha

Combination of lightning , TN-S, 100 kA (10/350 µs), 240 kA (8/20 µs)

0 reviews / Write a review

* Required fields



Related Product

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Spark gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 3+1 mode.Installa..

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

park gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 1+1 mode.Installat..

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of v..

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking.Combination of varistor lightning current ..