• Combination of lightning , TN-C, 7,5 kA (10/350 µs).

Pluggable module, visual fault signalling, module locking, onto 40 mm busbar system.

  • High performance lightning current arrester, installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards upstream power meters.
  • For protection against impact of direct or indirect lightning strikes in wide range of applications – houses, office or industrial buildings, resp. to sub- distribution boards in large buildings, for application in Germany.

Specifications:


Parameter name

Parameter value

Type of SPD

T1,T2,T3

Mounting

40 mm busbar system

Nominal voltage

Un

230 V AC

Maximum operating voltage

Uc

255.00 V AC

Type of network

TN

Maximum overcurrent protection

160 A gL/gG

Short-circuit current rating

ISCCR

25.0 kA

Total discharge current (10/350 µs)

ITotal(10/350)

22.50 kA

Lightning impulse current (10/350 µs)

Iimp

7.50 kA

Nominal discharge current (8/20 µs)

In

20.00 kA

Test voltage

Uoc

10.0 kV

Total discharge current (8/20 µs)

ITotal(8/20)

100.00 kA

Maximum discharge current (8/20 µs)

Imax

60.00 kA

Voltage protection level

Up

1.50 kV

Response time

ta

100 ns

TOV 5 s L-N

335 V

TOV characteristic (TOV 5 s)

withstand

TOV 120 min L-N

440 V

TOV characteristic (120 min)

withstand

Cross-section of connected conductors solid (min)

1.00 mm2

Cross-section of connected conductors solid (max)

35.00 mm2

Cross-section of connected conductors stranded (min)

1.00 mm2

Cross-section of connected conductors stranded (max)

25.00 mm2

Fault indication

red indication field

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC000381

Plug module

FLP-ZP-7,5-VBH/0

Customs tariff number

85363090

EAN

8595090566212


Dimensions:






Replacement module: FLP-ZP-7,5-VBH/0



Write a review

Note: HTML is not translated!
Captcha

Combination of lightning , TN-C, 7,5 kA (10/350 µs).

0 reviews / Write a review

* Required fields



Related Product

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)

Spark gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 3+1 mode.Installa..

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)

park gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 1+1 mode.Installat..

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of v..

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking.Combination of varistor lightning current ..