• DL-Cat. 5e 16 RACK PANEL

Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.

Technical specifications

Type of SPD

 

C2,C3

Location of SPD 

 

ST 3

Maximum operating voltage 

Uc

6V DC and 8V DC

Nominal load current

IL

0,100A

C2 nominal discharge current (8/20 µs) per core

In

0,20kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

1,60kA

C2 voltage protection level mode core-core at In 

Up

40V

C2 voltage protection level mode core-PE at In 

Up

350V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

65V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-core 

ta

100ns

Insertion attenuation at 250 MHz 

 

1,20dB

Connection (input - output)

 

RJ 45/RJ 45

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

60 °C

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC000943

Write a review

Note: HTML is not translated!
Captcha

DL-Cat. 5e 16 RACK PANEL

0 reviews / Write a review

* Required fields



Related Product

Galvanized steel ropes with round section, 6 x 36

Galvanized steel ropes with round section, 6 x 36

SpecificationPart NumberØ mm6 x 36(daN)(Kg/m)StandardJ508000WS86 x 364.0330,268500 - 1000J510000WS10..

Three-Phase Network Analyser - Class A

Three-Phase Network Analyser - Class A

Main Specifications: Voltage input: 3 channels: 0-275/400 VRMS (400/690 V available as an optio..

Test Cord 6P4C TO 4 Pole Test Plug Krone

Test Cord 6P4C TO 4 Pole Test Plug Krone

Test Cord 6P4C TO 4 Pole Test Plug Krone..

AED 14.69

VOLTASTEEL WIRE COVERED • ø 4 - 5 mm

VOLTASTEEL WIRE COVERED • ø 4 - 5 mm

Steel wire rod VOLTASTEEL WIRE COVERED, covered with PA, with interchangeable terminals M5,complete ..