Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the
boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.
Technical specifications
Type of SPD | C2,C3 | |
Location of SPD | ST 3 | |
Maximum operating voltage | Uc | 6V DC and 8V DC |
Nominal load current | IL | 0,100A |
C2 nominal discharge current (8/20 µs) per core | In | 0,20kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 1,60kA |
C2 voltage protection level mode core-core at In | Up | 40V |
C2 voltage protection level mode core-PE at In | Up | 350V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 65V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-core | ta | 100ns |
Insertion attenuation at 250 MHz | 1,50dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 60 °C | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC000943 |
DL-Cat. 5e 8 RACK PANEL
Related Product
Cable 1P, 18AWG, Shielded, PVC L40008-1A - 305m/Roll
2/C 18 AWG SHIELDED COMMERCIAL AUDIO, CONTROL AND INSTRUMENTATION CABLE80C 300V OR 60C 300V AWM STYL..
AED 1,261.78
KVM 8-Port 17" LCT (PS/2) Daisychainable
The CL1008 LCD KVM Switch series are control units that allow access to multiple computers from a si..
Galvanised steel cable roller
Specificationsø 110 - ø 75 ↔ 170 mm4,1 Kg300 x 240 x 250 mm..
Microflow Log - Intelligent Fiber Blowing Machine
The Microflow LOG is for blowing FTTH Fibers (EPFU) and Micro Cables. The Microflow LOG is a da..