Pluggable
module, visual fault signalling, module locking.
- Combination
of one-pole high performance lightning current arrester and encapsulated
efficiency spark gap, connected in the 1+1 mode.
- Installation
at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution
boards.
- For
protection against impact of director or indirect lightning strikes in wide
range of applications – houses, office and industrial buildings.
- Coordination with SPD type 2 (SLP-275 V) even without surge separating inductors, no leakage current.
Specifications:
|
Parameter name |
Parameter
value |
|
|
Type of SPD |
T1 |
|
|
Mounting |
DIN
rail 35 mm |
|
|
Nominal voltage |
Un |
230
V AC |
|
Maximum operating voltage L-N |
Uc |
260.00
V AC |
|
Maximum operating voltage N-PE |
Uc |
255.00
V AC |
|
Nominal load current for
"V" connection |
IL |
125
A |
|
Type of network |
TT |
|
|
Maximum overcurrent protection |
250
A gL/gG |
|
|
Maximum overcurrent protection for
"V" connection |
125
A gL/gG |
|
|
Short-circuit current rating |
ISCCR |
50.0
kA |
|
Total discharge current (10/350 µs) |
ITotal(10/350) |
50.00
kA |
|
Lightning impulse current (10/350
µs) L-N |
Iimp |
25.00
kA |
|
Lightning impulse current (10/350
µs) N-PE |
Iimp |
50.00
kA |
|
Voltage protection level mode L-N |
Up |
1.50
kV |
|
Voltage protection level mode L-PE |
Up |
2.20
kV |
|
Voltage protection level mode N-PE |
Up |
1.50
kV |
|
Ability to independently switch off
the following current N-PE |
Ifi |
0.1
kA |
|
Response time L-N |
ta |
100
ns |
|
Response time N-PE |
ta |
100
ns |
|
TOV 5 s L-N |
335
V |
|
|
TOV characteristic (TOV 5 s) |
withstand |
|
|
TOV 200 ms N-PE |
1
200 V |
|
|
TOV characteristic (TOV 200 ms) |
withstand |
|
|
Cross-section of connected
conductors solid (min) |
2.50
mm2 |
|
|
Cross-section of connected
conductors solid (max) |
50.00
mm2 |
|
|
Cross-section of connected conductors
stranded (min) |
2.50
mm2 |
|
|
Cross-section of connected
conductors stranded (max) |
35.00
mm2 |
|
|
Fault indication L-N |
red
indication field |
|
|
Fault indication N-PE |
no |
|
|
Remote indication |
no |
|
|
Degree of protection |
IP
20 |
|
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
|
Humidity |
5
- 95 % |
|
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
|
ETIM Class |
EC000381 |
|
|
Plug module |
FLP-25-T1-V/0|FLP-A50N
V/0 |
|
|
Customs tariff number |
85363090 |
|
|
EAN |
8595090562573 |
Dimensions:
Datasheet:
Combined lightning current arrester, 50 kA
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: FLP-25-T1-V/1+1
- MPN: FLP-25-T1-V/1+1
Terms & Conditions
- Product Information: Specifications, images and availability are subject to change without notice.
- Enquiries & Pricing: All enquiries and displayed prices are subject to availability and confirmation by Dafnia.
- Quotation & Payment: Final pricing, applicable taxes, delivery and payment terms will be stated in the quotation or invoice.
- Order Confirmation: Orders are confirmed only upon written acceptance by Dafnia and receipt of the agreed payment or approved purchase order, where applicable.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..