Pluggable module, visual fault signalling, module locking, terminals for supply, onto 40 mm busbar system, remote fault signalling.
- High performance lightning current arrester, installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards upstream power meters@for protection against impact of direct or indirect lightning strikes in wide range of applications – houses, office or industrial buildings, resp. to sub-distribution boards in large buildings @ protected supply of power meters assembly.
Specifications:
Parameter name |
Parameter
value |
|
|
Type of SPD |
T1,T2,T3 |
|
|
Mounting |
40
mm busbar system |
|
|
Nominal voltage |
Un |
230
V AC |
|
Maximum operating voltage |
Uc |
255.00
V AC |
|
Nominal load current - auxiliary
output terminals L, N |
6.3
A |
|
|
Type of network |
TN |
|
|
Maximum overcurrent protection |
160
A gL/gG |
|
|
Short-circuit current rating |
ISCCR |
25.0
kA |
|
Total discharge current (10/350 µs) |
ITotal(10/350) |
22.50
kA |
|
Lightning impulse current (10/350
µs) |
Iimp |
7.50
kA |
|
Nominal discharge current (8/20 µs) |
In |
20.00
kA |
|
Test voltage |
Uoc |
10.0
kV |
|
Total discharge current (8/20 µs) |
ITotal(8/20) |
100.00
kA |
|
Maximum discharge current (8/20 µs) |
Imax |
60.00
kA |
|
Voltage protection level |
Up |
1.50
kV |
|
Response time |
ta |
100
ns |
|
TOV 5 s L-N |
335
V |
|
|
TOV characteristic (TOV 5 s) |
withstand |
|
|
TOV 120 min L-N |
440
V |
|
|
TOV characteristic (120 min) |
withstand |
|
|
Cross-section of connected
conductors solid (min) |
1.00
mm2 |
|
|
Cross-section of connected
conductors solid (max) |
16.00
mm2 |
|
|
Cross-section of connected
conductors stranded (min) |
1.00
mm2 |
|
|
Cross-section of connected
conductors stranded (max) |
16.00
mm2 |
|
|
Cross-section of connected
conductors solid (max) - aux. out terminals L, N |
4.00
mm2 |
|
|
Cross-section of connected
conductors stranded (max) - aux. out terminals L, N |
2.50
mm2 |
|
|
Cross-section of remote indication
conductors solid (max) |
1.5
mm2 |
|
|
Cross-section of remote indication
conductors stranded (max) |
1.5
mm2 |
|
|
Fault indication |
red
indication field |
|
|
Remote indication |
potential-free
change-over contact |
|
|
Remote indication contacts |
250V/0,5A
AC,250V/0,1A DC |
|
|
Degree of protection |
IP
20 |
|
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
|
Humidity |
5
- 95 % |
|
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
|
ETIM Class |
EC000381 |
|
|
Plug module |
FLP-ZP-7,5-VBH/0 |
|
|
Customs tariff number |
85363090 |
|
|
EAN |
8595090570271 |
Dimensions:
Replacement Module:
Datasheet:
Combination of lightning ,TN-C, 7,5 kA (10/350 µs).
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: FLP-ZP2-7,5-VBH/3S
- MPN: FLP-ZP2-7,5-VBH/3S
Terms & Conditions
- Product Information: Specifications, images and availability are subject to change without notice.
- Enquiries & Pricing: All enquiries and displayed prices are subject to availability and confirmation by Dafnia.
- Quotation & Payment: Final pricing, applicable taxes, delivery and payment terms will be stated in the quotation or invoice.
- Order Confirmation: Orders are confirmed only upon written acceptance by Dafnia and receipt of the agreed payment or approved purchase order, where applicable.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..