Pluggable module, visual fault signalling, remote fault signalling.
- Varistor lightning current arrester.
- Installation at the boundary of zones LPZ 0 and LPZ 1 or higher, for objects in LPL III and IV.
- For protection against impact of partial lightning currents, induced overvoltages during a lightning strike or switching overvoltages.
Specifications:
Parameter name |
Parameter
value |
|
|
Type of SPD |
T1,T2 |
|
|
Mounting |
DIN
rail 35 mm |
|
|
Nominal voltage |
Un |
230
V AC |
|
Maximum operating voltage |
Uc |
275.00
V AC |
|
Maximum operating voltage |
Uc |
350.00
V DC |
|
Type of network |
TN |
|
|
Maximum overcurrent protection |
160
A gL/gG |
|
|
Short-circuit current rating |
ISCCR |
50.0
kA |
|
Lightning impulse current (10/350
µs) |
Iimp |
12.50
kA |
|
Nominal discharge current (8/20 µs) |
In |
30.00
kA |
|
Maximum discharge current (8/20 µs) |
Imax |
60.00
kA |
|
Voltage protection level |
Up |
1.50
kV |
|
Voltage protection level at 5 kA |
Up |
0.90
kV |
|
Response time |
ta |
25
ns |
|
TOV 5 s L-N |
335
V |
|
|
TOV characteristic (TOV 5 s) |
withstand |
|
|
Cross-section of connected
conductors solid (min) |
1.00
mm2 |
|
|
Cross-section of connected conductors
solid (max) |
35.00
mm2 |
|
|
Cross-section of connected
conductors stranded (min) |
1.00
mm2 |
|
|
Cross-section of connected
conductors stranded (max) |
25.00
mm2 |
|
|
Cross-section of remote indication
conductors solid (max) |
1.5
mm2 |
|
|
Cross-section of remote indication
conductors stranded (max) |
1.5
mm2 |
|
|
Fault indication |
red
indication field |
|
|
Remote indication |
potential-free
change-over contact |
|
|
Remote indication contacts |
250V/0,5A
AC,250V/0,1A DC |
|
|
Degree of protection |
IP
20 |
|
|
Range of ambient temperatures (min/max) |
-40
/ 80 °C |
|
|
Humidity |
5
- 95 % |
|
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
|
ETIM Class |
EC001457 |
|
|
Plug module |
FLP-12,5
V/0 |
|
|
Customs tariff number |
85363090 |
|
|
EAN |
8595090534228 |
Dimensions:
Replacement Module:
Datasheet:
Lightning current and surge arrester, 12.5 kA (10/350 µs), 60 kA (8/20 µs)
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: FLP-12,5 V/1 S
- MPN: FLP-12,5 V/1 S
Terms & Conditions
- Product Information: Specifications, images and availability are subject to change without notice.
- Enquiries & Pricing: All enquiries and displayed prices are subject to availability and confirmation by Dafnia.
- Quotation & Payment: Final pricing, applicable taxes, delivery and payment terms will be stated in the quotation or invoice.
- Order Confirmation: Orders are confirmed only upon written acceptance by Dafnia and receipt of the agreed payment or approved purchase order, where applicable.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..