Pluggable module, visual fault signalling, remote fault signalling.
- Varistor lightning current arrester.
- Installation at the boundary of zones LPZ 0 and LPZ 1 or higher.
- For protection against impact of partial lightning currents, induced overvoltages during a lightning strike or switching overvoltages.
Specifications:
Parameter name |
Parameter
value |
|
Type of SPD |
T1,T2 |
|
Mounting |
DIN
rail 35 mm |
|
Nominal voltage |
Un |
48÷60
V AC/DC |
Maximum operating voltage |
Uc |
75.00
V AC |
Maximum operating voltage |
Uc |
75.00
V DC |
Type of network |
TN |
|
Maximum overcurrent protection |
160
A gL/gG |
|
Short-circuit current rating |
ISCCR |
25.0
kA |
Lightning impulse current (10/350
µs) |
Iimp |
12.50
kA |
Nominal discharge current (8/20 µs) |
In |
20.00
kA |
Maximum discharge current (8/20 µs) |
Imax |
40.00
kA |
Voltage protection level |
Up |
0.45
kV |
Response time |
ta |
25
ns |
Cross-section of connected
conductors solid (min) |
1.00
mm2 |
|
Cross-section of connected
conductors solid (max) |
35.00
mm2 |
|
Cross-section of connected
conductors stranded (min) |
1.00
mm2 |
|
Cross-section of connected
conductors stranded (max) |
25.00
mm2 |
|
Cross-section of remote indication
conductors solid (max) |
1.5
mm2 |
|
Cross-section of remote indication
conductors stranded (max) |
1.5
mm2 |
|
Fault indication |
red
indication field |
|
Remote indication |
potential-free
change-over contact |
|
Remote indication contacts |
250V/0,5A
AC,250V/0,1A DC |
|
Degree of protection |
IP
20 |
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
Humidity |
5
- 95 % |
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
ETIM Class |
EC000381 |
|
Plug module |
FLP-12,5-075-VH/0 |
|
Customs tariff number |
85363030 |
|
EAN |
8595090541691 |
Dimensions:
Replacement module: FLP-12,5-075-VH/0
Single-pole lightning current and surge arrester, 48 - 60 V
Related Product
Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)
Spark gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 3+1 mode.Installa..
Lightning current arrester between N and PE , TT system, 50 kA (10/350 µs)
park gap for N-PE, pluggable module, module locking.For connection Type 1 SPD in 1+1 mode.Installat..
Lightning current and surge arrester ,TT, 50 kA (10/350 µs), 100 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of v..
Lightning current and surge arrester , TT, 50 kA (10/350 µs), 100 kA (8/20 µs)
Pluggable module, visual fault signalling, module locking.Combination of varistor lightning current ..