Visual fault signalling.
- Universally applicable SPD for all types of LV electric and electronic equipments against surge voltage.
- Installation to LV installations, close to protected equipment.
- For protection of the equipments against impact of induced overvoltages during a lightning strike or switching overvoltages.
Specifications:
Parameter name | Parameter value | |
Type of SPD | T3 | |
Mounting | DIN rail 35 mm | |
Nominal voltage | Un | 60 V AC |
Maximum operating voltage | Uc | 75.00 V AC |
Nominal load current | IL | 25.000 A |
Type of network | TN | |
Maximum overcurrent protection | 25 A gL/gG or B 25 A | |
Short-circuit current rating | ISCCR | 1.5 kA |
Residual current | IPE | 0.005 mA |
Nominal discharge current (8/20 µs) L-N | In | 2.00 kA |
Nominal discharge current (8/20 µs) L+N-PE | In | 2.00 kA |
Nominal discharge current (8/20 µs) N-PE | In | 2.00 kA |
Test voltage L-N | Uoc | 4.0 kV |
Test voltage L+N-PE | Uoc | 4.0 kV |
Test voltage N-PE | Uoc | 4.0 kV |
Voltage protection level mode L-N | Up | 0.43 kV |
Voltage protection level mode L-PE | Up | 0.75 kV |
Voltage protection level mode N-PE | Up | 0.75 kV |
Response time L-N | ta | 25 ns |
Response time N-PE | ta | 100 ns |
TOV 5 s L-N | 120 V | |
TOV characteristic (TOV 5 s) | withstand | |
Cross-section of connected conductors solid (max) | 6.00 mm2 | |
Cross-section of connected conductors stranded (max) | 6.00 mm2 | |
Fault indication | red indicator | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 80 °C | |
Humidity | 5 - 95 % | |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
ETIM Class | EC000942 | |
Customs tariff number | 85363010 | |
EAN | 8595090560944 |
Datasheet:
Surge protection,TN and TT systems, 25 A, up to 75 V AC
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: DA-075-DJ25
- MPN: DA-075-DJ25
Terms & Conditions
- Product Information: Specifications, images and availability are subject to change without notice.
- Enquiries & Pricing: All enquiries and displayed prices are subject to availability and confirmation by Dafnia.
- Quotation & Payment: Final pricing, applicable taxes, delivery and payment terms will be stated in the quotation or invoice.
- Order Confirmation: Orders are confirmed only upon written acceptance by Dafnia and receipt of the agreed payment or approved purchase order, where applicable.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..