• DM-PROFIBUS 5 V

Protection of line and communication interfaces of the PROFIBUS industrial bus-bar system. Coarse and fine surge protection. Also, cable shielding is protected.

Parameters

Type of SPD

 

C2,C3

Connection (input - output) 

 

terminals-terminals

Location of SPD 

 

ST 2+3

Nominal voltage 

Un

5V DC

Maximum operating voltage

Uc

6V AC

Maximum operating voltage

Uc

8V AC

Nominal load current

IL

0,060 A

C2 nominal discharge current (8/20 µs) core-core 

In

10,00Ka

C2 voltage protection level mode core-core at In 

Up

150 V

C2 voltage protection level mode core-COM at In 

Up

150 V

C2 voltage protection level mode COM-PE at In 

Up

350 V

C2 voltage protection level mode SH-PE at In 

Up

350 V

C3 voltage protection level mode core-core at 1 kV/µ

Up

40 V

C3 voltage protection level mode core-COM at 1 kV/µs

Up

40 V

C3 voltage protection level mode COM-PE at 1 kV/µs

Up

650 V

C3 voltage protection level mode SH-PE at 1 kV/µs

Up

650 V

Response time core-core 

ta

1 ns

Response time core COM

 

1 ns

Response time COM-PE

ta

100ns

Response time SH-PE 

ta

100ns

Serial resistance per core 

R

1,00Ω

Treshold frequency core-core

f

100,00MHz

Cross-section of connected conductors solid - max 

 

400 mm2

Cross-section of connected conductors stranded - max 

 

2,50 mm2

Degree of protection

 

Write a review

Note: HTML is not translated!
Captcha

DM-PROFIBUS 5 V

0 reviews / Write a review

* Required fields



Related Product

Patch Cord CAT6 UTP 24AWG 2m PVC - Blue

Patch Cord CAT6 UTP 24AWG 2m PVC - Blue

Category 6 U/UTP Patch CordsUnshielded Twisted Pair (UTP) Category 6 Patch Cord conforms to ANSI/TIA..

AED 5.80

Ratcheting Cable Crimper / Stripper / Cutter For Pass-Thru

Ratcheting Cable Crimper / Stripper / Cutter For Pass-Thru

·         Modular crimp-connector installation tool for voi..

Hydraulic tensioners for overhead lines stringing

Hydraulic tensioners for overhead lines stringing

Hydraulic machine suitable to string the conductors or OPGW of overhead transmission ..

Universal disconnection rail LSA

Universal disconnection rail LSA

Universal disconnection rail LSA 2/10. Universal disconnection rail LSA 2/10.Specifications:Param..