• DP-060-V/1-16

Protection of power supply with output from the midle and non-grounded pole. Installation as close as possible to the protected equipment.

Technical specifications

Type of SPD

 

T3, C2

Connection (input - output) 

 

terminals-terminals

Location of SPD 

 

ST 2

Nominal voltage

Un

60V AC

Maximum operating voltage 

Uc

75V AC

Nominal load current 

IL

16,000A

C2 nominal discharge current (8/20 µs) per core 

In

2,00kA

C2 voltage protection level mode core-core at In

Up

390V

C2 voltage protection level mode core-PE at In 

Up

210v

Test voltage L+ - L- 

 

4,0kV

Test voltage L+(L-)-PE 

 

4,0kV

voltage protection level L+ - L- 

 

0,39 kV

voltage protection level L+(L-)-PE

 

0,21 kV

Maximum overcurrent protection 

 

16 A gL/gG or B 16 A

Response time L+ - L-

 

25ns

Response time L+(L-)-PE 

 

100ns

Cross-section of connected conductors solid (min) 

 

0,14mm2

 

Cross-section of connected conductors solid (max) 

 

4,00 mm2

Cross-section of connected conductors stranded (min) 

 

0,14 mm2

Cross-section of connected conductors stranded (max)

 

2,50 mm2

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

-70 °C

Mounting 

 

DIN rail 35 mm

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012, EN 61643-11:2012, IEC 61643-11:2011


Write a review

Note: HTML is not translated!
Captcha

DP-060-V/1-16

0 reviews / Write a review

* Required fields



Related Product

Earthing Bar For 27U Cabinet

Earthing Bar For 27U Cabinet

 Earthing Bar For 27U Cabinet..

Standard Socket Power Cords

Standard Socket Power Cords

C14 to C13 (Left Bend)10A, 250V; UL, CSA & VDE Approvals..

Cable Coax DIGISAT 523 ELITE - 100m

Cable Coax DIGISAT 523 ELITE - 100m

Inner Conductor: 99,99% pure electrolitic annealed bare copper (annealed=thermal softening proc..

AED 2.72

PRO2™ Switched POPS STV-6501 20-30A/16-32A 208V/230V 3-Ph (24) C13 &(6) C19

PRO2™ Switched POPS STV-6501 20-30A/16-32A 208V/230V 3-Ph (24) C13 &(6) C19

The Server Technology® PRO2 Switched POPS CDU provides control of outlet power and local LED input c..

AED 11,180.00