- Lightning current arrester of 2-core signalling lines.
- Installation at the boundary of LPZ 0 and LPZ 1 zones at the line entry into building.
- Mainly for protection of telecommunication lines against surge voltage.
Specifications:
| Parameter name | Parameter value | |
| Type
  of SPD | D1,C2 | |
| Location
  of SPD | ST 1 | |
| Mounting | DIN rail 35 mm | |
| Maximum
  operating voltage | Uc | 128.00 V AC | 
| Maximum
  operating voltage | Uc | 180.00 V DC | 
| Nominal
  load current | IL | 1.600 A | 
| Treshold
  frequency core-core | f | 120.00 MHz | 
| D1
  impulse discharge current (10/350 µs) per core | Iimp | 2.50 kA | 
| D1
  total discharge current (10/350 µs) cores-PE | ITotal | 5.00 kA | 
| C2
  nominal discharge current (8/20 µs) per core | In | 10.00 kA | 
| C2
  total discharge current (8/20 µs) cores-PE | ITotal | 20.00 kA | 
| C3
  voltage protection level mode core-PE at 1 kV/µs | Up | 550 V | 
| C3
  voltage protection level mode core-core at 1 kV/µs | Up | 550 V | 
| Response
  time core-core | ta | 100 ns | 
| Response
  time core-PE | ta | 100 ns | 
| Connection
  (input - output) | terminals-terminals | |
| Cross-section
  of connected conductors solid (max) | 6.00 mm2 | |
| Cross-section
  of connected conductors stranded (max) | 6.00 mm2 | |
| Degree
  of protection | IP 20 | |
| Range
  of ambient temperatures (min/max) | -40 / 70 °C | |
| According
  to standard | EN 61643-21+A1,A2:2013, IEC
  61643-21+A1,A2:2012 | |
| ETIM
  Class | EC001466 | |
| Customs
  tariff number | 85363010 | |
| EAN | 8595090558224 | 
Dimensions:
Lightning current arrester for signalling lines, max. 180 V
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..