V – Varistor, screw terminals.
- Single-stage surge arrester.
- Installation close to protected equipment.
- For the protection of signaling, data, and other lines against the impact of surge voltage.
Specifications:
| Parameter name | Parameter value | ||
| Type
  of SPD | C2 | 
 | |
| Location
  of SPD | ST 2 | 
 | |
| Mounting | DIN rail 35 mm | 
 | |
| Maximum
  operating voltage | Uc | 140.00 V AC | 
 | 
| Maximum
  operating voltage | Uc | 180.00 V DC | 
 | 
| Nominal
  load current | IL | 16.000 A | 
 | 
| C2
  nominal discharge current (8/20 µs) per core | In | 6.00 kA | 
 | 
| C2
  voltage protection level mode core-PE at In | Up | 530 V | 
 | 
| Response
  time core-PE | ta | 25 ns | 
 | 
| Connection
  (input - output) | terminals-terminals | 
 | |
| Cross-section
  of connected conductors solid (min) | 0.14 mm2 | 
 | |
| Cross-section
  of connected conductors solid (max) | 4.00 mm2 | 
 | |
| Cross-section
  of connected conductors stranded (min) | 0.14 mm2 | 
 | |
| Cross-section
  of connected conductors stranded (max) | 2.50 mm2 | 
 | |
| Range
  of ambient temperatures (min/max) | -40 / 70 °C | 
 | |
| According
  to standard | EN 61643-21+A1,A2:2013, IEC
  61643-21+A1,A2:2012 | 
 | |
| ETIM
  Class | EC000943 | 
 | |
| Customs
  tariff number | 85363010 | 
 | |
| EAN | 8595090551515 | 
 | |
Dimensions:
Single stage surge arrester – Varistor, screw terminal, 180 V DC
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.