Fine
protector for Ethernet networks with PoE and general structured cabling.
- Fine
surge protector for Ethernet networks with PoE and general structured cabling.
- LPZ
1 - LPZ 2 boundary installation.
- To protect devices working with signals over twisted pairs up to 60 V.
Specifications:
| Parameter name | Parameter
   value | |
| Type of SPD | C2,C3 | |
| Location of SPD | ST
  2+3 | |
| Mounting | DIN
  rail 35 mm | |
| Maximum operating voltage core-core | Uc | 60
  V DC | 
| Maximum operating voltage pair-pair
  (POE) | Uc | 60
  V DC | 
| Nominal load current per core at 25
  °C | IL | 0.5
  A | 
| Treshold frequency core-core | f | 500.00
  MHz | 
| Insertion attenuation at treshhold
  frequency | 2.90
  dB | |
| C2 nominal discharge current (8/20
  µs) core-core | In | 0.20
  kA | 
| C2 total discharge current (8/20 µs)
  cores-PE | ITotal | 1.60
  kA | 
| C2 voltage protection level mode
  core-core (@Uoc/In) | Up | 130,00
  (0,4 kV / 0,2 kA) | 
| C2 voltage protection level mode
  core-PE (@Uoc/In) | Up | 400,00
  V (0,4 kV / 0,2 kA) | 
| C2 voltage protection level mode
  pair-pair (POE) (@Uoc/In) | Up | 130,00
  V (0,4 kV / 0,2 kA) | 
| C3 voltage protection level mode
  core-core (@In - 1 kV/µs) | Up | 130,00
  V (10 A) | 
| C3 voltage protection level mode
  core-PE (@In - 1 kV/µs) | Up | 600,00
  V (10 A) | 
| C3 voltage protection level mode
  pair-pair (POE) (@In - 1 kV/µs) | Up | 130,00
  V (10 A) | 
| Response time core-core | ta | 1
  ns | 
| Response time core-PE | ta | 100
  ns | 
| Connection (input - output) | RJ45/RJ45 | |
| Degree of protection | IP
  30 (without connectors IP 10) | |
| Range of ambient temperatures
  (min/max) | -10
  / 50 °C | |
| Humidity | 15
  - 85 % | |
| According to standard | EN
  61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 | |
| ETIM Class | EC000943 | |
| Customs tariff number | 85363030 | |
| EAN | 8595090571087 | 
Dimensions:
Fine surge protector, LPZ 1 - LPZ 2 boundary installation, up to 60v
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..