For general
structured cabling networks.
- Combined
(2-stage) SPD for general structured cabling networks.
- LPZ
0 to LPZ 1 boundary installation.
- To protect devices working with signals over twisted pairs up to 60 V.
Specifications:
| Parameter name | Parametervalue | |||
| Type
  of SPD | D1,C2,C3 | |||
| Location
  of SPD | ST 1+2+3 | |||
| Mounting | DIN rail 35 mm | |||
| Maximum
  operating voltage core-core | Uc | 60,00 V DC | ||
| Maximum
  operating voltage pair-pair (POE) | Uc | 60,00 V DC | ||
| Nominal
  load current per core at 25 °C | IL | 0.5 A | ||
| Treshold
  frequency core-core | f | 250.00 MHz | ||
| Insertion
  attenuation at treshhold frequency | 1.50 dB | |||
| C2
  nominal discharge current (8/20 µs) core-core | In | 0.15 kA | ||
| D1
  total discharge current (10/350 µs) cores-PE | ITotal | 2.00 kA | 
 | |
| C2
  total discharge current (8/20 µs) cores-PE | ITotal | 10.00 kA | ||
| C2
  voltage protection level mode core-core (@Uoc/In) | Up | 120,00 V (0,3 kV / 0,15 kA) | ||
| C2
  voltage protection level mode core-PE (@Uoc/In) | Up | 700,00 V (2,5 kV / 1,25 kA) | ||
| C2
  voltage protection level mode pair-pair (POE) (@Uoc/In) | Up | 90,00 V (0,3 kV / 0,15 kA) | ||
| C3
  voltage protection level mode core-core (@In - 1 kV/µs) | Up | 110,00 V (10 A) | ||
| C3
  voltage protection level mode core-PE (@In - 1 kV/µs) | Up | 500,00 V (10 A) | ||
| C3
  voltage protection level mode pair-pair (POE) (@In - 1 kV/µs) | Up | 85,00 V (10 A) | ||
| Response
  time core-core | ta | 1 ns | ||
| Response
  time core-PE | ta | 100 ns | ||
| Connection
  (input - output) | RJ 45/RJ 45 | |||
| Degree
  of protection | IP 30 (without connectors IP 10) | |||
| Range
  of ambient temperatures (min/max) | -10 / 50 °C | |||
| Humidity | 15 - 85 % | |||
| According
  to standard | EN 61643-21+A1,A2:2013, IEC
  61643-21+A1,A2:2012 | |||
| ETIM
  Class | EC000943 | |||
| Customs
  tariff number | 85363010 | |||
| EAN | 8595090570691 | |||
Dimensions:
SPD for general structured cabling networks,60 V, LPZ 0-1 and higher.
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..