LPZ 1 and higher, Ethernet without PoE
- Fine surge protection.
- Installation at protected device inside LPZ1 and higher (not suitable for LPZ 0).
- For pprotection of Ethernet networks (up to Cat.6A) without PoE.
- Installation into DL-PL-RACK-1U box.
- DL-...-M with front output.
- DL-...-R-M with rear output.
- Not applicable for Ethernet with PoE.
Specifications:
Parameter
name |
Parameter value |
|
Type of SPD |
C2,C3 |
|
Location of SPD |
ST 2+3 |
|
Mounting |
DL-PL-RACK-1U |
|
Maximum operating
voltage |
Uc |
6.00 V AC |
Maximum operating
voltage |
Uc |
8.50 V DC |
Maximum operating
voltage POE |
Uc |
6.00 V AC |
Maximum operating
voltage POE |
Uc |
8.50 V DC |
Nominal load current
per core at 25 °C |
IL |
0.5 A |
Treshold frequency core-core |
f |
500.00 MHz |
Insertion attenuation
at treshhold frequency |
2.90 dB |
|
C2 nominal discharge
current (8/20 µs) per core |
In |
0.20 kA |
C2 total discharge
current (8/20 µs) cores-PE |
ITotal |
1.60 kA |
C2 voltage protection
level mode (POE) at In |
Up |
55.00 V |
C2 voltage protection
level mode core-PE at In |
Up |
400 V |
C2 voltage protection
level mode core-core at In |
Up |
55 V |
C3 voltage protection
level mode (POE) at 1 kV/µs |
30.00 V |
|
C3 voltage protection
level mode core-PE at 1 kV/µs |
Up |
600 V |
C3 voltage protection
level mode core-core at 1 kV/µs |
Up |
30 V |
Response time
core-core |
ta |
1 ns |
Response time core-PE |
ta |
100 ns |
Connection (input -
output) |
RJ 45/RJ 45 |
|
Degree of protection |
IP 20 |
|
Range of ambient
temperatures (min/max) |
-40 / 80 °C |
|
Humidity |
5 - 95 % |
|
According to standard |
EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 |
|
Customs tariff number |
85363010 |
|
EAN |
8595090541967 |
Dimensions:
SPD for high-speed Ethernet networks, LPZ 1 and higher
Related Product
Universal disconnection rail LSA
Universal disconnection rail LSA 2/10. Universal disconnection rail LSA 2/10.Specifications:Param..
Mounting frame – 1 position for CLSA
Mounting frame – 1 position. Mounting frame – 1 position for CLSA.Specifications: ..
Empty module cover
SPD - for data, signalling and telecommunications lines / ICT / Ethernet and PoE - for 19" RACKprote..
Comb grounding rail for CLSA.
Comb grounding rail for CLSA.Specifications: Parameter name Para..