N connectors, 50 Ohm.
- Lightning current arrester for coaxial line.
- Installation at the boundary of LPZ 0 and LPZ
1 zones at the line entry into building.
- For protection of telecommunication equipment
against impact of direct or indirect lightning strike.
- Suitable for the combined signal and power supply distribution.
Specifications:
| ameter name | Parameter value | |
| Type
  of SPD | D1,C2 | |
| Location
  of SPD | ST 1+2 | |
| Maximum
  operating voltage | Uc | 70.00 V DC | 
| Nominal
  load current | IL | 6.000 A | 
| Frequency
  range | f | 0,00 - 3800,00 MHz | 
| Impedance | Z | 50 Ω | 
| Power
  (CW) | P | 40.00 W | 
| Insertion
  loss typ. (max.) | A | 0,2 (0,4) dB | 
| VSWR typ.
  (max.) | VSWR | 1,1 (1,2) | 
| D1
  impulse discharge current (10/350 µs) core-PE | Iimp | 2.50 kA | 
| C2
  nominal discharge current (8/20 µs) core-PE | In | 10.00 kA | 
| Dynamic
  spark-over voltage at 1kV/µs | Udyn | 700.00 V | 
| Response
  time core-PE | ta | 100 ns | 
| Connection
  (input - output) | N 50 | |
| Degree
  of protection | IP 66 | |
| Range
  of ambient temperatures (min/max) | -40 / 80 °C | |
| According
  to standard | EN 61643-21+A1,A2:2013, IEC
  61643-21+A1,A2:2012 | |
| ETIM
  Class | EC001466 | |
| Customs
  tariff number | 85363030 | |
| EAN | 8595090533467 | 
Dimensions:
Lightning current arrester for coaxial lines (antennas), 70 V DC
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..