Pluggable module, visual fault signalling, module locking, remote fault signalling.
- Encapsulated high-performance spark gap.
- Installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards.
- For protection against impact of direct or indirect lightning strikes in the hardest application in heavy, chemical and energy industry.
- Coordination with SPD type 2 (SLP-275 V) even without surge separating inductors.
Specifications:
| Parameter name | Parameter
   value | |
| Type of SPD | T1 | |
| Mounting | DIN
  rail 35 mm | |
| Nominal voltage | Un | 230
  V AC | 
| Maximum operating voltage | Uc | 255.00
  V AC | 
| Nominal load current for
  "V" connection | IL | 125
  A | 
| Type of network | TN | |
| Maximum overcurrent protection | 315
  A gL/gG | |
| Maximum overcurrent protection for
  "V" connection | 125
  A gL/gG | |
| Short-circuit current rating | ISCCR | 50.0
  kA | 
| Residual current | IPE | 0.550
  mA | 
| Lightning impulse current (10/350
  µs) | Iimp | 50.00
  kA | 
| Nominal discharge current (8/20 µs) | In | 50.00
  kA | 
| Voltage protection level | Up | 2.50
  kV | 
| Ability to independently switch off
  the following current | Ifi | 50.0
  kA | 
| Response time | ta | 100
  ns | 
| TOV 5 s L-N | 335
  V | |
| TOV 5 s L-PE | 440
  V | |
| TOV characteristic (TOV 5 s) | withstand | |
| TOV 120 min L-N | 440
  V | |
| TOV 120 min L-PE | 335
  V | |
| TOV characteristic (120 min) | withstand | |
| Cross-section of connected
  conductors solid (min) | 2.50
  mm2 | |
| Cross-section of connected
  conductors solid (max) | 50.00
  mm2 | |
| Cross-section of connected
  conductors stranded (min) | 2.50
  mm2 | |
| Cross-section of connected
  conductors stranded (max) | 35.00
  mm2 | |
| Cross-section of remote indication
  conductors solid (max) | 1.5
  mm2 | |
| Cross-section of remote indication
  conductors stranded (max) | 1.5
  mm2 | |
| Fault indication | red
  indication field | |
| Remote indication | potential-free
  change-over contact | |
| Remote indication contacts | 250V/0,5A
  AC,250V/0,1A DC | |
| Degree of protection | IP
  20 | |
| Range of ambient temperatures
  (min/max) | -40
  / 80 °C | |
| Humidity | 5
  - 95 % | |
| According to standard | EN
  61643-11:2012, IEC 61643-11:2011 | |
| ETIM Class | EC000381 | |
| Plug module | FLP-SG50
  VS/0 | |
| Customs tariff number | 85363090 | |
| EAN | 8595090540533 | 
Dimensions:
Lightning current arrester for TN or TT system, 50 kA
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..