F connectors 75 ohm.
- Surge arrester, shielding connected to
protective grounding.
- Installation close to protected equipment.
- For protection of sensitive coaxial inputs of commercial receivers (TV/SAT).
Specifications:
| Parameter name | Parameter value | |
| Type
  of SPD | D1,C2,C3 | |
| Location
  of SPD | ST 1+2+3 | |
| Mounting | DIN rail 35 mm | |
| Maximum
  operating voltage | Uc | 26.00 V DC | 
| Nominal
  load current | IL | 0.700 A | 
| Frequency
  range | f | 0,00 - 2300,00 MHz | 
| Impedance | Z | 75 Ω | 
| Insertion
  loss | 1.50 dB | |
| VSWR typ.
  (max.) | VSWR | 1,7 | 
| D1
  impulse discharge current (10/350 µs) core-PE | Iimp | 0.50 kA | 
| C2
  nominal discharge current (8/20 µs) core-PE | In | 2.50 kA | 
| Dynamic
  spark-over voltage at 1kV/µs | Udyn | 85.00 V | 
| Response
  time core-PE | ta | 1 ns | 
| Connection
  (input - output) | F 75 | |
| Degree
  of protection | IP 20 | |
| Range
  of ambient temperatures (min/max) | -40 / 80 °C | |
| Humidity | 5 - 95 % | |
| According
  to standard | EN 61643-21+A1,A2:2013, IEC
  61643-21+A1,A2:2012 | |
| ETIM
  Class | EC001625 | |
| Customs
  tariff number | 85363010 | |
| EAN | 8595090541585 | 
Dimensions:
Surge arrester for protection of sensitive coaxial inputs ,75 Ohm
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..